Panasonic 4585 COM loop repeater

Panasonic

Panasonic 4585 COM loop repeater

Product code 41272

COM loop repeater installed in the 4466 external power supply. The repeater amplifies the loop signal and forms a sub-loop with a cable length of up to 1,100 m.

  • Extends the COM loop with a sub-loop, cable length up to 1,100 m
  • Sub-loop current draw max. 350 mA
  • Installed in the 4466 power supply, two repeaters per power supply
  • Automatic addressing via EBLWin
  • Monitors the sub-loop for open-circuit and short-circuit faults
  • EN 54-18, VdS G219025

The product sheet opens in a new tab, where you can print or save it.

A quote or help choosing products? Sales+358 40 668 7641myynti@pap.fi

A technical question about a device? Technical support+358 40 668 7643tuki@pap.fi

Product description

Panasonic 4585 is a COM loop repeater that allows the loop of an addressable fire alarm system to be extended further than the control panel’s own loop would allow. The repeater amplifies the loop signal and forms a sub-loop (SUB-loop) from it, with a maximum length of 1,100 m when the conductor resistance of the cable is 24 Ω/km. Standard addressable COM loop devices are connected to the sub-loop.

The repeater is a circuit board installed inside the 4466 external power supply. One power supply can hold two repeaters. The repeater receives its 24 V DC operating voltage from the power supply, and up to 350 mA of current is available for the sub-loop. The repeater has no short-circuit isolator of its own; instead, the COM loop is protected by the short-circuit isolator of the 4466 power supply. The repeater monitors the sub-loop and reports open circuits, short circuits, undervoltage and internal faults to the control panel.

Installation and compatibility

The repeater works with the EBL512 G3 control panel (software version 2.5 or later) in Advanced mode. The address is set automatically via the 4466 power supply: the repeater is given the power supply address +1 or +2, depending on which output it is connected to. The sub-loop is connected to screw terminals that accept conductors of Ø 0.65–1.6 mm (0.33–2 mm²). If no devices are connected to the repeater, the sub-loop must be closed. The repeater is intended for dry indoor areas.

Technical data

Product code
41272
Manufacturer
Panasonic
Product group
Fire alarm systems › Field devices › I/O units
Dimensions
108 × 114 × 15 mm
Operating voltage
16–30 V DC (nominal 24 V DC from power supply 4466)
Weight
55 g
Operating temperature
−5…+40 °C
EN 54 approval
EN 54-18
VdS approval
G219025
CPR
0786-CPR-21627
Current consumption
Max. 640 mA, < 6 mA from the COM loop
Sub-loops
22–24 V DC, max. 350 mA
Cable length
Max. 1,100 m (24 Ω/km)
Humidity
Max. 95% RH, non-condensing
Connection
Screw terminal, conductor Ø 0.65–1.6 mm (0.33–2 mm²)