Skip to content
PAP Group, part of ProseroPAP Group, part of Prosero
Search the site

Suggested searches

Quick links

Request a quote
MenuClose
Panasonic 4464 expansion board with two voltage outputs

Panasonic

Panasonic 4464 expansion board with two voltage outputs

Product code 41271

Addressable expansion board for the 4466 power supply: two supervised 24 V DC outputs for alarm devices, an output for closing fire doors and a general-purpose input. The board is addressed automatically.

  • Installed inside the 4466 power supply, max. 2 boards
  • 2 supervised 24 V DC outputs for alarm devices (EN 54-13)
  • Fire door output VO2 and parallel relay contact RE2
  • General-purpose input, e.g. for monitoring fire door closure
  • Automatic addressing via the 4466 power supply
  • Approved to EN 54-18 and by VdS (G219025)

The product sheet opens in a new tab, where you can print or save it.

A quote or help choosing products? Sales+358 40 668 7641myynti@pap.fi

A technical question about a device? Technical support+358 40 668 7643tuki@pap.fi

Product description

Panasonic 4464 is an addressable expansion board with two voltage outputs, installed inside the 4466 external power supply. The board receives a 24 V DC supply from the power supply and is protected against loop short circuits by the short-circuit isolator of the power supply. Up to two expansion boards can be installed in one power supply.

Outputs VO0 and VO1 are programmable 24 V DC alarm device outputs. When supervised, they detect short circuits and open circuits in accordance with EN 54-13 when the 4472 end-of-line device is installed at the end of the line; no calibration is required. Output VO2 is intended for closing fire doors: it is controlled by a control expression, and it cuts the voltage approximately 30 seconds after a mains failure or loss of loop communication. Relay contact RE2 (2 A 30 V DC) is controlled at the same time. General-purpose input IN0 can monitor fire door closure, for example. Each output is max. 1 A, with a total of max. 2 A; with simplified 10 kΩ supervision an output can be 2 A, but EN 54-13 is then not met.

Installation and compatibility

  • Attached to charger board 4467 inside the 4466 power supply; screws included
  • The address is assigned automatically: power supply address +1 or +2
  • Advanced mode: EBL512 G3 and EBL128 V ≥ 2.5
  • Conductor size Ø 0.65–1.6 mm (0.33–2 mm²)

Technical data

Product code
41271
Manufacturer
Panasonic
Product group
Fire alarm systems › Field devices › I/O units
Dimensions
108 × 114 × 15 mm
Operating voltage
24 V DC from power supply 4466 (16–30 V DC); loop 12–30 V DC
Weight
59 g
Operating temperature
−5…+40 °C
EN 54 approval
EN 54-18
VdS approval
G219025
CPR
0786-CPR-21627
Storage temperature
−20…+70 °C
Humidity
Max. 95% RH, non-condensing
Material
Polycarbonate
Current consumption (quiescent)
≤ 15 mA (24 V), < 6 mA from the loop
Outputs
VO0 and VO1 supervised, VO2 for fire doors; each max. 1 A, total 2 A; RE2 2 A 30 V DC
Inputs
1 general input, supervision with 10 kΩ end-of-line resistor
Address range
001–253 (automatic)
Short-circuit isolator
No (isolator in power supply 4466)
Compatibility
EBL512 G3, EBL128 V ≥ 2.5
Mounting
Expansion board for power supply 4466
Standards
EN 55032, EN 50130-4, EN IEC 63000 (RoHS)

Documents

Original manufacturer documents (PDF).

More products in this product group

Need help choosing products?

Our sales team will help you choose devices that suit the site and the existing system, and will prepare a quotation. Tell us about the system, the site and the quantities needed.

Contact sales +358 40 668 7641