Panasonic 3364 I/O unit, supervised 24 V outputs

Panasonic

Panasonic 3364 I/O unit, supervised 24 V outputs

Product code 41370

Addressable voltage output unit with two supervised 24 V DC outputs for alarm devices and one output for closing fire doors. Connected to the COM loop and an external 24 V supply.

  • Two programmable, supervised 24 V DC outputs for alarm devices
  • Separate 24 V DC output for fire door holding magnets
  • Door output is cut approx. 30 s after a mains or loop fault
  • Outputs max. 1 A continuous
  • Approved to EN 54-18, CPR 0786-CPR-21201
  • DIN rail mounting with the 3363 accessory

The product sheet opens in a new tab, where you can print or save it.

A quote or help choosing products? Sales+358 40 668 7641myynti@pap.fi

A technical question about a device? Technical support+358 40 668 7643tuki@pap.fi

Product description

Panasonic 3364 is an addressable unit with two supervised voltage outputs for Panasonic EBL fire alarm control panels. The unit is connected to the COM loop, and the operating voltage for the outputs is taken from an external 24 V DC power supply. It is suitable, for example, for controlling sounders and beacons and for releasing fire door holding magnets in dry indoor areas.

The unit has three outputs. VO0 and VO1 are programmable and supervised, intended for sounders, beacons and other alarm devices. Line supervision is based on 470 nF capacitors, and the value is calibrated from the control panel menu; an open circuit, a short circuit or a deviation from the calibrated value is reported as a fault. VO2 is an unsupervised output for closing fire doors. It is controlled by a control expression, and it also cuts the voltage after approximately 30 seconds if the /Mains OK input reports a mains fault or communication on the COM loop is lost. The outputs are programmed with the EBLWin software.

Installation and compatibility

  • The address (001–253) is set with the 4414 address setting tool
  • Compatible with EBL512 G3, EBL128 and EBL512 (V ≥ 2.2)
  • Wall or ceiling mounting, 10 cable entries in the cover
  • DIN rail mounting with the 3363 adapter kit
  • One 5098 end-of-line device is required for each supervision capacitor
  • Conductor size Ø 0.6–1.6 mm (0.28–2 mm²)

Technical data

Product code
41370
Manufacturer
Panasonic
Product group
Fire alarm systems › Field devices › I/O units
Weight
110 g (with protective cover 155 g)
Dimensions
90 × 70 × 32 mm (with protective cover 129 × 73 × 45 mm)
Operating voltage
12–30 V DC from the loop (nominal 24 V DC); external supply 18–30 V DC
Operating temperature
−10…+55 °C
EN 54 approval
EN 54-18
CPR
0786-CPR-21201
Storage temperature
−20…+60 °C
Humidity
Max. 95% RH, non-condensing
Colour
Dark grey
Material
Flame-retardant ABS and polycarbonate
IP rating
IP54
Current consumption (quiescent)
< 6 mA
Current consumption (alarm)
< 6 mA
Outputs
VO0 and VO1 supervised, VO2 unsupervised; each max. 1 A (10 ms 1.4 A)
Address range
001–253
Short-circuit isolator
No
Mounting
Surface mounting on wall or ceiling, DIN rail with accessory 3363
Standards
EN 61000-6-3, EN 50130-4, EN IEC 63000 (RoHS)