Panasonic
Panasonic 4445 addressable local alarm acknowledgement button
Product code 41416
Addressable local alarm acknowledgement button for apartments and similar premises. The resident acknowledges a local smoke alarm and airs the room before the alarm is transmitted to the fire brigade.
- Reduces unnecessary alarms to the fire brigade
- Acknowledgement time 10–120 s and investigation time 1–9 min programmable
- 1–5 smoke detectors and a base sounder per LAA group
- Up to 100 LAA groups (EBL512 G3, EBLOne), 50 (EBL128)
- Wall mounting with frame or flush mounting in a 65 mm box
✓ In quote request: pcs ·
✓ On your document list · Select and download documents
The product sheet opens in a new tab, where you can print or save it.
A quote or help choosing products? Sales+358 40 668 7641myynti@pap.fi
A technical question about a device? Technical support+358 40 668 7643tuki@pap.fi
Product description
Panasonic 4445 is an addressable local alarm acknowledgement button (LAAU) that is connected to the COM loop. It is installed, for example, in an apartment or similar premises together with a smoke detector and a base sounder. When the detector detects smoke, the base sounder sounds locally and the red LED of the button lights up.
If the green button is pressed within the acknowledgement time (10–120 s, default 30 s), the local sound is silenced and the investigation time (1–9 min, default 3 min) begins, during which the smoke can be aired out. If the detectors return to normal within the investigation time, the alarm ends. Otherwise, or if the button is not pressed, the control panel gives a normal fire alarm, which is transmitted to the fire brigade and the alarm systems. The acknowledgement can be programmed to be repeatable up to three times.
One LAA group consists of 1–5 analogue smoke detectors (4401, 4401I, 4400, 4400I or wireless 4611), at least one buzzer, such as base sounder 4479, and one acknowledgement button. From EBLWin 2.4.1 onwards, a whole detection zone can be connected to an LAA group. With multi-sensor detectors 4400 and 4400I, the function can be set to be aborted by a heat alarm (56 °C).
Installation
- Wall mounting with frame or flush mounting in a 65 mm round box
- The address 001–253 and NORMAL mode are set with tool 3314 or 4414 before connection to the loop
- All devices in an LAA group must be on the same control panel
Technical data
- Product code
- 41416
- Manufacturer
- Panasonic
- Product group
- Fire alarm systems › Field devices › I/O units
- Weight
- 39 g
- Dimensions
- 84 × 84 × 22 mm
- IP rating
- IP43
- Operating temperature
- −10…+55 °C
- EN 54 approval
- Designed to meet the requirements of EN 54-18:2005
- Storage temperature
- −25…+70 °C
- Humidity
- Max. 90% RH, non-condensing
- Colour
- White
- Material
- Flame-retardant ABS and polycarbonate
- Operating voltage
- 12–30 V DC
- Current consumption (quiescent)
- < 2 mA
- Current consumption (alarm)
- < 5 mA
- Acknowledgement time
- 10–120 s (programmable)
- Investigation time
- 1–9 min (programmable)
- Address range
- 001–253
- Short-circuit isolator
- No
- Compatibility
- EBL512 G3, EBLOne, EBL128
- Mounting
- Wall mounting with frame or flush mounting in a 65 mm box
- Standards
- EN 61000-6-3, EN 50130-4, EN IEC 63000 (RoHS)
Documents
Original manufacturer documents (PDF).
Technical datasheets
Certificates and declarations
More products in this product group
Need help choosing products?
Our sales team will help you choose devices that suit the site and the existing system, and will prepare a quotation. Tell us about the system, the site and the quantities needed.




