Skip to content
PAP Group, part of ProseroPAP Group, part of Prosero
Search the site

Suggested searches

Quick links

Request a quote
MenuClose
Panasonic 4445 addressable local alarm acknowledgement button

Panasonic

Panasonic 4445 addressable local alarm acknowledgement button

Product code 41416

Addressable local alarm acknowledgement button for apartments and similar premises. The resident acknowledges a local smoke alarm and airs the room before the alarm is transmitted to the fire brigade.

  • Reduces unnecessary alarms to the fire brigade
  • Acknowledgement time 10–120 s and investigation time 1–9 min programmable
  • 1–5 smoke detectors and a base sounder per LAA group
  • Up to 100 LAA groups (EBL512 G3, EBLOne), 50 (EBL128)
  • Wall mounting with frame or flush mounting in a 65 mm box

The product sheet opens in a new tab, where you can print or save it.

A quote or help choosing products? Sales+358 40 668 7641myynti@pap.fi

A technical question about a device? Technical support+358 40 668 7643tuki@pap.fi

Product description

Panasonic 4445 is an addressable local alarm acknowledgement button (LAAU) that is connected to the COM loop. It is installed, for example, in an apartment or similar premises together with a smoke detector and a base sounder. When the detector detects smoke, the base sounder sounds locally and the red LED of the button lights up.

If the green button is pressed within the acknowledgement time (10–120 s, default 30 s), the local sound is silenced and the investigation time (1–9 min, default 3 min) begins, during which the smoke can be aired out. If the detectors return to normal within the investigation time, the alarm ends. Otherwise, or if the button is not pressed, the control panel gives a normal fire alarm, which is transmitted to the fire brigade and the alarm systems. The acknowledgement can be programmed to be repeatable up to three times.

One LAA group consists of 1–5 analogue smoke detectors (4401, 4401I, 4400, 4400I or wireless 4611), at least one buzzer, such as base sounder 4479, and one acknowledgement button. From EBLWin 2.4.1 onwards, a whole detection zone can be connected to an LAA group. With multi-sensor detectors 4400 and 4400I, the function can be set to be aborted by a heat alarm (56 °C).

Installation

  • Wall mounting with frame or flush mounting in a 65 mm round box
  • The address 001–253 and NORMAL mode are set with tool 3314 or 4414 before connection to the loop
  • All devices in an LAA group must be on the same control panel

Technical data

Product code
41416
Manufacturer
Panasonic
Product group
Fire alarm systems › Field devices › I/O units
Weight
39 g
Dimensions
84 × 84 × 22 mm
IP rating
IP43
Operating temperature
−10…+55 °C
EN 54 approval
Designed to meet the requirements of EN 54-18:2005
Storage temperature
−25…+70 °C
Humidity
Max. 90% RH, non-condensing
Colour
White
Material
Flame-retardant ABS and polycarbonate
Operating voltage
12–30 V DC
Current consumption (quiescent)
< 2 mA
Current consumption (alarm)
< 5 mA
Acknowledgement time
10–120 s (programmable)
Investigation time
1–9 min (programmable)
Address range
001–253
Short-circuit isolator
No
Compatibility
EBL512 G3, EBLOne, EBL128
Mounting
Wall mounting with frame or flush mounting in a 65 mm box
Standards
EN 61000-6-3, EN 50130-4, EN IEC 63000 (RoHS)

Documents

Original manufacturer documents (PDF).

Certificates and declarations

More products in this product group

Need help choosing products?

Our sales team will help you choose devices that suit the site and the existing system, and will prepare a quotation. Tell us about the system, the site and the quantities needed.

Contact sales +358 40 668 7641