Panasonic
Panasonic 2841 intrinsically safe analogue heat detector
Product code 41576
Intrinsically safe addressable analogue heat detector for potentially explosive atmospheres (zones 0, 1 and 2). The detector is connected to the COM loop via IS isolator unit 2842.
- ATEX II 1 G Ex ia IIC T5 Ga, zones 0/1/2
- Addressable, for EBL512 G3, EBLOne and EBL128 panels
- Up to 20 IS detectors per isolator unit 2842
- Three alarm algorithms: A1, A2S and BS
- IP66/67 with mounting base 2843
- EN 54-5, VdS G223019
✓ In quote request: pcs ·
✓ On your document list · Select and download documents
The product sheet opens in a new tab, where you can print or save it.
A quote or help choosing products? Sales+358 40 668 7641myynti@pap.fi
A technical question about a device? Technical support+358 40 668 7643tuki@pap.fi
Product description
Panasonic 2841 is an intrinsically safe (IS) addressable analogue heat detector installed in potentially explosive atmospheres in zones 0, 1 and 2. The detector works like the analogue heat detector 3308/3309: the temperature is measured with a thermistor, and a fire alarm is indicated by the detector’s LED.
One of three alarm algorithms in accordance with EN 54-5 is selected for the detector in EBLWin: class A1 (alarm at 56 °C, or as early as 46 °C with a rapid rise in temperature), A2S (60 °C) or BS (74 °C). The detector operates in NORMAL mode in EBL512 G3 and EBL128 panels and in EBLOne panels from version 3.3 onwards, and its address (001–253) is set with the 4414 or 4414E address setting tool before connection.
Installation and compatibility
The detector is connected to an IS COM line, which is connected to the COM loop via IS isolator unit 2842 installed outside the hazardous area. Up to 20 IS detectors 2840 or 2841 can be connected to one isolator unit. The IS COM line is radial without a return conductor, its length can be up to 500 m, and it does not need an end-of-line resistor. The detector is mounted on the ceiling either on its own (IP22) or in the watertight mounting base 2843, giving an IP rating of IP66/67. The detector is intended to be tested, for example, with Solo or Testifire test equipment.
Technical data
- Product code
- 41576
- Manufacturer
- Panasonic
- Product group
- Fire alarm systems › Field devices › Ex detectors
- Colour
- Grey
- Weight
- 325 g
- Dimensions
- Ø 102 × 65 mm
- LED
- Red
- Operating temperature
- −10…+55 °C
- IP rating
- IP22, IP66/67 with mounting box 2843
- EN 54 approval
- EN 54-5
- ATEX certificate
- DEKRA 11ATEX0107 X
- ATEX classification
- II 1 G Ex ia IIC T5 Ga
- CPR
- 0786-CPR-21784
- Material
- Flame-retardant ABS and polycarbonate
- Operating voltage
- 15–17.3 V DC (nominal 16 V DC, IS COM line)
- Current consumption (quiescent)
- ≤ 0.3 mA
- Current consumption (alarm)
- ≤ 1.5 mA
- Humidity
- Max. 95% RH, non-condensing
- Alarm temperature
- A1: 56 °C (rapid rise 46 °C), A2S: 60 °C, BS: 74 °C
- Connection
- Push-in terminals, conductor 0.08–2 mm²
- VdS approval
- G223019
Documents
Original manufacturer documents (PDF).
Technical datasheets
Certificates and declarations
- EU declaration of conformity, no. ESSC-F00018-10
- Declaration of performance (DoP), no. 0786-CPR-21784 (document ID ESSC-FP0018-12)
- CPR certificate of constancy of performance, no. 2831-CPR-F2749 (issue 02)
- CPR certificate of constancy of performance, no. 0786-CPR-21784
- EU-type examination certificate (ATEX), no. DEKRA 11ATEX0107 X, issue 3
- VdS approval, no. G 223019 (dated 2 June 2023)
- VdS approval, no. G 223019 (dated 18 July 2025)