Panasonic 2811 ATEX heat detector DCD-1E-IS
Product code 41550
Intrinsically safe (IS) conventional heat detector for hazardous areas. A rate-of-rise detector that also has a fixed trigger temperature of 60 °C.
- ATEX II 1 G Ex ia IIC T5 Ga, category 1 (zones 0, 1 and 2)
- Rate-of-rise and 60 °C fixed temperature detection
- Two indicators, 360° visibility
- Remote indicator connection
- Mounting base without electronics
- LPCB, GL and IECEx approvals
✓ In quote request: pcs ·
✓ On your document list · Select and download documents
The product sheet opens in a new tab, where you can print or save it.
A quote or help choosing products? Sales+358 40 668 7641myynti@pap.fi
A technical question about a device? Technical support+358 40 668 7643tuki@pap.fi
Product description
Panasonic 2811 (Hochiki DCD-1E-IS) is an intrinsically safe conventional heat detector for hazardous areas such as chemical plants, paint factories and other process facilities handling flammable gases. The detector responds to a rapid rise in temperature and also has a fixed trigger temperature of 60 °C.
The detector is ATEX rated II 1 G Ex ia IIC T5 Ga (−20 °C ≤ Ta ≤ +55 °C), so it is suitable for category 1 areas and all lower categories. A device designed to be intrinsically safe does not store enough energy to produce a spark or an igniting surface temperature, even in a fault condition. The two indicators are visible from all directions, and the detector has a remote indicator output. The manufacturer also offers a white version of the detector, DCD-1E-IS(WHT).
Installation
The detector is installed in a mounting base without electronics (e.g. the 2812 ATEX mounting base). The conventional zone line in the Ex area is connected to the fire alarm control panel via a Zener barrier or galvanic isolator (e.g. MTL5561, 2820) located in the safe area. Up to 20 IS detectors can be connected to one zone line.
Technical data
- Product code
- 41550
- Manufacturer
- Panasonic
- Product group
- Fire alarm systems › Field devices › Ex detectors
- Weight
- 97 g
- Dimensions
- Ø 100 × 40 mm
- IP rating
- IP63
- ATEX certificate
- BAS01ATEX1021X
- ATEX classification
- II 1 G Ex ia IIC T5 Ga (−20 °C ≤ Ta ≤ +55 °C)
- Operating voltage
- 15–30 V DC
- Operating temperature
- −10…+55 °C
- Manufacturer’s code
- Hochiki DCD-1E-IS
- Detection principle
- Rate of rise + fixed 60 °C
- Approvals
- LPCB, GL, IECEx