Panasonic 2820 ATEX galvanic isolator MTL5561

Panasonic

Panasonic 2820 ATEX galvanic isolator MTL5561

Product code 41530

Two-channel galvanic isolator (MTL5561) for conventional fire and smoke detectors located in a hazardous area. The isolator is installed in the safe area.

  • Two isolated, loop-powered channels
  • Detectors can be located in zone 0, gas group IIC
  • Protected against reverse polarity
  • SIL2 (single), SIL3 (redundant), IEC 61508
  • Input voltage 6–30 V DC, current range 1–40 mA

The product sheet opens in a new tab, where you can print or save it.

A quote or help choosing products? Sales+358 40 668 7641myynti@pap.fi

A technical question about a device? Technical support+358 40 668 7643tuki@pap.fi

Product description

Panasonic 2820 is the Eaton MTL5561 galvanic isolator, intended for connecting conventional fire and smoke detectors when the detectors are located in a hazardous area. The isolator limits the energy fed into the Ex area and galvanically isolates the hazardous-area and safe-area circuits from each other. The isolator itself is installed in the safe area.

The device has two isolated channels that are loop-powered and require no separate supply. When a detector in the Ex area is activated, the current on the safe-area side changes accordingly and the fire alarm control panel detects the alarm. The detectors can be located in zone 0, gas group IIC (temperature classes T4–T6), provided that they are certified for this. The input is protected against reverse polarity.

The isolator has been assessed to the functional safety standard IEC 61508: as a single device it is suitable for SIL2 applications and, when connected redundantly, for SIL3 applications. Power dissipation is no more than 0.7 W per channel at 24 V with a 40 mA signal.

Applications

  • Conventional IS smoke and heat detectors in Ex areas, e.g. the 2811 ATEX heat detector

Technical data

Product code
41530
Manufacturer
Panasonic
Product group
Fire alarm systems › Field devices › Ex detectors
Manufacturer’s code
Eaton MTL5561
Channels
2, galvanically isolated, loop-powered
Operating voltage
6–30 V DC
Current range
1–40 mA
Quiescent current
< 400 µA / channel (24 V)
Power dissipation
Max. 0.7 W (24 V, 40 mA) / 0.9 W (30 V, 40 mA) per channel
Response time
Settles to within 5% in 1.5 ms
Hazardous area
Detectors in Zone 0, IIC, T4–T6 (with certified detectors)
Safety parameters
Uo = 28 V, Io = 93 mA, Po = 0.65 W, Um = 253 V
SIL
SIL2 (HFT = 0), SIL3 (HFT = 1), IEC 61508:2010