Skip to content
PAP Group, part of ProseroPAP Group, part of Prosero
Search the site

Suggested searches

Quick links

Request a quote
MenuClose
E2S IS-mA1-R mini sounder ATEX/IECEx/FM, IP65

E2S

E2S IS-mA1-R mini sounder ATEX/IECEx/FM, IP65

Product code 42072

Compact, intrinsically safe (Ex ia) sounder for zone 0 hazardous areas. Sound level 100 dB(A), 49 tones and IP65; also approved to EN 54-3.

  • 100 dB(A) / 1 m, audible range 40 m (1 kHz)
  • ATEX, IECEx and FM: Ex ia IIC T4 Ga, zone 0
  • EN 54-3 approved fire alarm sounder (0786-CPD-20338, tones 2, 3, 9, 15, 16 and 17)
  • 49 tones, 3 alarm stages, volume control
  • Certified end-of-line resistor
  • IP65, weighs only 0.36 kg

The product sheet opens in a new tab, where you can print or save it.

A quote or help choosing products? Sales+358 40 668 7641myynti@pap.fi

A technical question about a device? Technical support+358 40 668 7643tuki@pap.fi

Product description

E2S IS-mA1 is a compact, intrinsically safe (Ex ia) sounder certified to ATEX, IECEx and EAC Ex for zone 0 applications and FM-approved for Class I, Division 1 and Class I, Zone 0 applications. It is suitable for fire alarm systems, security systems and process control. According to the declaration of performance, the sounder meets EN 54-3, the standard for fire alarm sounders (EC type-examination certificate 0786-CPD-20338, VdS). This model is red (RAL 3000).

Operation

The nominal sound output is 100 dB(A) at 1 metre, with an audible range of approximately 40 m (1 kHz). There are 49 selectable tones (UKOOA/PFEER compatible), and each can be switched externally to a second or third alarm stage. The volume is adjustable in the range 90–100 dB(A). The tones of multiple sounders synchronise automatically, and the input is protected against overload and reverse polarity. The end-of-line resistor is certified.

Installation and power supply

The sounder is powered via a certified Zener barrier or galvanic isolator (16–28 V DC) whose output parameters do not exceed Uo 28 V, Io 93 mA and Po 660 mW. Typical current consumption is 25 mA (24 V supply, 28 V / 300 Ω barrier). The enclosure has two M20 cable entry knockouts, the terminals accept 0.5–2.5 mm² conductors, and the fixings are stainless steel. A separate IS-mA1M version is available for mining environments (Group I).

Technical data

Product code
42072
Manufacturer
E2S
Product group
Fire alarm systems › Field devices › Alarm devices
Colour
Red (RAL 3000)
Weight
0.36 kg
IP rating
IP65
ATEX classification
II 1G Ex ia IIC T4 Ga (−40 °C ≤ Ta ≤ +60 °C)
ATEX certificate
Sira 05ATEX2084X
IECEx certificate
IECEx SIR 06.0045X
FM approval
IS Class I, Division 1, Groups A, B, C, D; Class I, Zone 0, AEx ia IIC T4
EN 54 approval
EN 54-3, type B (tones 2, 3, 9, 15, 16 and 17; 18–28 V DC)
CPR
0786-CPD-20338
Sound output
100 dB(A) / 1 m ±3 dB (tone 2), adjustable 90–100 dB(A)
Audible range
40 m (1 kHz)
Tones
49 (UKOOA/PFEER), 3 alarm stages
Operating voltage
16–28 V DC via a Zener barrier or galvanic isolator
Current consumption (alarm)
25 mA typical (24 V, barrier 28 V / 300 Ω)
Ex supply parameters
Uo ≤ 28 V, Io ≤ 93 mA, Po ≤ 660 mW
Material
Flame-retardant ABS (UL94 V0 & 5VA)
Operating temperature
−40…+60 °C
Humidity
90% RH (+20 °C)
Connection
Terminals 0.5–2.5 mm², 2 × M20 entry knockouts
MTBF
273.1 years (MIL 217)

Documents

Original manufacturer documents (PDF).

Technical datasheets

Installation guides

More products in this product group

Need help choosing products?

Our sales team will help you choose devices that suit the site and the existing system, and will prepare a quotation. Tell us about the system, the site and the quantities needed.

Contact sales +358 40 668 7641