Panasonic 4480WH addressable wall-mounted beacon, white

Panasonic

Panasonic 4480WH addressable wall-mounted beacon, white

Product code 41392

Addressable EN 54-23 wall-mounted beacon with a built-in short-circuit isolator. Coverage W-2.4-5.0, i.e. 5 × 5 m, for corridors, offices and toilets, for example.

  • Coverage W-2.4-5.0 (5 × 5 m, 60 m³) at high power
  • Low power: class O, 2.5 × 2.5 m (13 m³)
  • Flash rate 0.5 or 1 Hz, selected in EBLWin
  • Built-in short-circuit isolator, powered from the COM loop
  • Supports automatic addressing
  • Approved to EN 54-23 and EN 54-17 and by VdS (G217003)

The product sheet opens in a new tab, where you can print or save it.

A quote or help choosing products? Sales+358 40 668 7641myynti@pap.fi

A technical question about a device? Technical support+358 40 668 7643tuki@pap.fi

Product description

Panasonic 4480WH is a white addressable wall-mounted beacon, i.e. a visual alarm device (VAD) to EN 54-23. It has a red LED and a built-in short-circuit isolator, and it takes its operating voltage from the COM loop. It is suitable for indoor use (type A), for example in corridors, offices, toilets and other public spaces.

Coverage and flash rate are selected in EBLWin. At high power, the coverage class is W-2.4-5.0, i.e. the beacon covers an area of 5.0 × 5.0 m (60 m³) when the LED is at a height of no more than 2.4 m. At low power, the class is O (2.5 × 2.5 m, 13 m³), in which case the LED is installed at a height of no more than 2.1 m. The flash rate is set to 0.5 Hz or 1 Hz. The beacons are not synchronised with each other.

The built-in short-circuit isolator does not require its own COM loop address. It divides the loop into segments, so a short circuit disables only the faulty segment and the other devices continue to operate normally.

Installation and compatibility

  • Wall mounting, LED at a height of no more than 2.4 m; gasket between the device and the wall, screws not included
  • Automatic addressing with EBLWin or manually with the 4414/4414E tool (address 001–253)
  • Advanced mode: EBL512 G3 and EBL128 V ≥ 2.3, EBLOne V ≥ 3.3
  • Conductor size Ø 0.6–1.4 mm (0.3–1.5 mm²)

Technical data

Product code
41392
Manufacturer
Panasonic
Product group
Fire alarm systems › Field devices › Alarm devices
Colour
White
Weight
100 g
Dimensions
Ø 93 × 65 mm
Flash rate
0.5 or 1 Hz
Operating temperature
−10…+55 °C
EN 54 approval
EN 54-23, EN 54-17
VdS approval
G217003
CPR
0786-CPR-21531
Storage temperature
−25…+70 °C
Humidity
Max. 95% RH, non-condensing
Material
Flame-retardant ABS and polycarbonate
IP rating
IP21C
Operating voltage
12–30 V DC (nominal 24 V DC)
Current consumption (quiescent)
2.5 mA
Current consumption (alarm)
High power 65 mA (1 Hz) / 34 mA (0.5 Hz), low power 35 mA (1 Hz) / 23 mA (0.5 Hz)
Input power
0.03–2.0 W
Light source
Red LED
Coverage
W-2.4-5.0 (5 × 5 m, 60 m³); low power O (2.5 × 2.5 m, 13 m³)
Synchronisation
No
Address range
001–253
Short-circuit isolator
Built-in
Compatibility
EBL512 G3, EBL128 V ≥ 2.3, EBLOne V ≥ 3.3
Mounting
Wall mounting, max. 2.4 m, indoors (type A)
Standards
EN 61000-6-3, EN 50130-4, EN IEC 63000 (RoHS)