Skip to content
PAP Group, part of ProseroPAP Group, part of Prosero
Search the site

Suggested searches

Quick links

Request a quote
MenuClose
Loudspeaker line card: green circuit board, white relays and a long green screw terminal strip

Ambient System

Ambient System SMART-xCtrLine-44 loudspeaker line card, 4 lines

Product code SMART-xCtrLine-44

Loudspeaker line control card for four loudspeaker circuits in the smartVES system. A different audio message can be routed to each output. Line monitoring by impedance, as a loop or with an EOL module.

  • 4 loudspeaker circuits, each with its own audio message
  • AB, loop or single-zone wiring
  • Line measurement by impedance, as a loop or with an EOL module
  • CPR 1438-CPR-0948 as part of the smartVES system

The product sheet opens in a new tab, where you can print or save it.

A quote or help choosing products? Sales+358 40 668 7641myynti@pap.fi

A technical question about a device? Technical support+358 40 668 7643tuki@pap.fi

Product description

SMART-xCtrLine-44 is a loudspeaker line control card of Ambient System’s smartVES system. Independent audio messages from the system’s audio buses can be routed to its four outputs. The card controls up to four loudspeaker circuits. The circuits can be wired as AB zones, as a loop or as single zones. Different audio content can be sent to each circuit.

The load of the loudspeaker line can be measured by the impedance method, as a loop with short-circuit isolators or with end-of-line (EOL) modules. According to the manufacturer, impedance measurement has been extended compared with earlier control cards. The card is powered from the backplane of the central unit.

Technical data

Product code
SMART-xCtrLine-44
Manufacturer
Ambient System
Product group
Voice alarm systems › Control equipment
Outputs
4 loudspeaker circuits
Measurement methods
Impedance, loop with short-circuit isolators, end-of-line (EOL) module
Impedance measurement frequency
1–48 kHz
EOL module signal frequency
18–24 kHz
Maximum measurable current
2 A
Maximum measurable voltage
200 V
Measurement accuracy
Max. 5%
Power supply
From the central unit backplane
Current consumption
Max. 152 mA (48 V)
Connector
10-pole screw terminal (Phoenix, 5.08 mm), included
EN 54 approval
EN 54-16 (as part of the smartVES system)
CPR
1438-CPR-0948
Operating temperature
−5…+40 °C
Humidity
15–80%
Storage temperature
−20…+70 °C
Dimensions
70 × 215 × 30 mm

Documents

Original manufacturer documents (PDF).

User manuals

Compatible products

Need help choosing products?

Our sales team will help you choose devices that suit the site and the existing system, and will prepare a quotation. Tell us about the system, the site and the quantities needed.