Skip to content
PAP Group, part of ProseroPAP Group, part of Prosero
Search the site

Suggested searches

Quick links

Request a quote
MenuClose
Loudspeaker line card: green circuit board, red relays and metal front plate with a green screw terminal

Ambient System

Ambient System ABT-xCtrLine-2 loudspeaker line card, 2 lines

Product code ABT-xCrtLine-2

Loudspeaker line control card for two independent loudspeaker lines (A and B) for a control card slot of the central unit. Switching between main and standby amplifier, line monitoring. EN 54-16.

  • Two independent loudspeaker line outputs (A and B)
  • Switching between main and standby amplifier
  • Line measurement by impedance, as a loop or with an EOL module
  • Detects faults, open circuits and earth faults

The product sheet opens in a new tab, where you can print or save it.

A quote or help choosing products? Sales+358 40 668 7641myynti@pap.fi

A technical question about a device? Technical support+358 40 668 7643tuki@pap.fi

Product description

ABT-xCtrLine-2 is a loudspeaker line control card from Ambient System with two independent loudspeaker line outputs (A and B). In PAP’s product list, the code is written as ABT-xCrtLine-2. The card switches the lines between the main and standby amplifiers.

The line measurement method is selected in the software settings: impedance, loop or end-of-line (EOL) module. The card detects faults, line breaks and earth faults. According to the smartVES system datasheet, the card fits the control card slot of all central units.

Technical data

Product code
ABT-xCrtLine-2
Manufacturer
Ambient System
Manufacturer’s code
ABT-xCtrLine-2
Product group
Voice alarm systems › Control equipment
Outputs
2 loudspeaker lines (A, B)
Measurement methods
Impedance, loop, end-of-line (EOL) module
Impedance measurement frequency
1–48 kHz
EOL module signal frequency
18–24 kHz
Maximum measurable current
20 A
Maximum measurable voltage
200 V
Measurement accuracy
Max. 5%
Power supply
From the central unit backplane
Current consumption
121 mA (48 V)
Connector
6-pole screw terminal (Phoenix, 5.08 mm), included
Card slot
Control card slot
Operating temperature
0…+60 °C
Humidity
15–80% (non-condensing)
Storage temperature
−20…+70 °C
Dimensions
70 × 215 × 30 mm
EN 54 approval
EN 54-16 (as part of the system)
CPR
1488-CPR-0500/W (MultiVES), 1438-CPR-0948 (smartVES)

Documents

Original manufacturer documents (PDF).

Technical datasheets

User manuals

Compatible products

Need help choosing products?

Our sales team will help you choose devices that suit the site and the existing system, and will prepare a quotation. Tell us about the system, the site and the quantities needed.

Contact sales +358 40 668 7641