Panasonic
Panasonic 5001SPFI EBL512 G3, 4 loops, without display
Product code 41031
EBL512 G3 fire alarm control panel without display, with four COM loops. The panel is intended for distributed systems in which it is operated over the network from a panel with a display.
- 4 COM loops, up to 1,012 addresses and 512 alarm points
- No front panel or display – operated over the network from a 5000 panel
- Up to 30 panels in the network, copper or fibre link
- Up to 128 short-circuit isolators per loop
- Space for internal batteries 2 × 12 V, 17–28 Ah
- EN 54-2 and EN 54-4
✓ In quote request: pcs ·
✓ On your document list · Select and download documents
The product sheet opens in a new tab, where you can print or save it.
A quote or help choosing products? Sales+358 40 668 7641myynti@pap.fi
A technical question about a device? Technical support+358 40 668 7643tuki@pap.fi
Product description
Panasonic EBL512 G3 5001 is an intelligent, analogue addressable fire alarm control panel without a front panel, display or door. The panel without display is used in distributed systems in those parts of the building where local operation of the panel is not needed. It does not operate stand-alone but is connected via the network to a system that has at least one EBL512 G3 5000 panel with a display.
The panel has four COM loops, each of which can take up to 253 loop devices. The panel can be configured for 128, 256 or 512 alarm points, and a total of 1,012 addresses are available. The loop current is up to 350 mA, and each loop can be extended with four sub-loops using the COM loop repeater 4585. There can be up to 128 short-circuit isolators per loop. The panel also has four programmable monitored voltage outputs, two programmable relay outputs, four programmable inputs and relay outputs for fire and fault transmission.
Network and installation
The panels are connected to each other with the network board 5040 (EBL Ring network) or the TLON communication board 5090. Up to 30 panels can be connected to the same network, and the network can be implemented as a redundant copper or fibre cable network. The panel is wall-mounted; mounting plates are also available for a 19-inch rack (5020) and for a combustible surface (5021). Two 12 V 17–28 Ah batteries fit inside the panel; larger batteries (up to 65 Ah) are placed outside the panel. Batteries are not included in the delivery. The panel is intended for dry indoor spaces.
Technical data
- Product code
- 41031
- Manufacturer
- Panasonic
- Product group
- Fire alarm systems › Control equipment
- COM loop
- 4 (max. 350 mA / loop)
- Sub-loops
- Up to 16 sub-loops using a COM loop repeater
- Programmable voltage output
- 4
- Relay output
- 2
- Supervised input
- 4
- Voltage output
- 6
- Weight
- 19 kg (without batteries), 41 kg (with batteries)
- Dimensions
- 625 × 418 × 177 mm
- Battery
- 2 × 12 V, 17–28 Ah inside the panel, max. 2 × 65 Ah external
- IP rating
- IP30
- Operating temperature
- −5…+40 °C
- EN 54 approval
- EN 54-2, EN 54-4
- CPR
- 0402-CPR-C500143, 0402-CPR-C500142
- Colour
- Light grey (NCS S 1500-N)
- Material
- Aluminium-zinc coated steel (AZ150)
- Operating voltage
- 230 V AC (195–253 V), 50 Hz
- Humidity
- Max. 95% RH, non-condensing
- Capacity
- Max. 1,012 addresses, 512 alarm points
Documents
Original manufacturer documents (PDF).
Technical datasheets
User manuals
Design guides
Certificates and declarations
- VdS system approval, no. S 214004
- VdS approval, no. G 210058
- CNBOP-PIB certificate of admittance (Poland), no. 5011/2023
- CPR certificate of constancy of performance, no. 0786-CPR-20982
- CPR certificate of constancy of performance, no. 0402-CPR-C500142
- CPR certificate of constancy of performance, no. 0402-CPR-C500143
- EU declaration of conformity, no. D09-MFST-290-09
- Declaration of performance (DoP), no. D09-MFST-P291 (version 05)
More products in this product group



- CommFront
Need help choosing products?
Our sales team will help you choose devices that suit the site and the existing system, and will prepare a quotation. Tell us about the system, the site and the quantities needed.