Panasonic 1105 loop tester

Panasonic

Panasonic 1105 loop tester

Product code 41040

Loop tester for testing, troubleshooting and commissioning a COM loop before the fire alarm control panel is installed. Connected between the loop and a computer and operated with EBLWin.

  • Checks loop cabling and devices before the panel is installed
  • Automatic addressing with the EBLWin wizard
  • Detects open circuits, short circuits, L/C mix-ups and duplicate addresses
  • Signable PDF report for loop documentation
  • SSD configuration directly from the scanned loop
  • 24 V DC power supply included

The product sheet opens in a new tab, where you can print or save it.

A quote or help choosing products? Sales+358 40 668 7641myynti@pap.fi

A technical question about a device? Technical support+358 40 668 7643tuki@pap.fi

Product description

Panasonic 1105 Loop Tester is a loop tester for testing, troubleshooting and commissioning a COM loop before the fire alarm control panel has been installed. The tester is connected between the COM loop and a computer, and it can be used to quickly verify the cabling and loop devices during installation. This is useful, for example, when the installation is carried out by a subcontractor.

The Scan loop function in EBLWin finds all devices connected to the loop except expansion boards and shows the loop graphically and as a list. The tester detects open circuits, short circuits, mixed-up L/C conductors and duplicate addresses. The scanned loop can be saved as an XML file, used to create an SSD configuration directly and printed as a PDF report containing the devices’ current consumption, technical number, sequence number and serial number. The report is signed and included in the handover documentation.

The tester can also set the addresses of loop devices automatically. From EBLWin version 2.10.0 onwards, the 1105 wizard guides you through loop scanning and addressing. Devices with an isolator receive addresses 1–128 and devices without an isolator 129–248.

Use

The tester is earthed to the nearest protective earth point and connected to the COM loop, to a 24 V power supply and to the computer with a USB cable. Logging in to EBLWin requires the EBLWin key 5094.

Technical data

Product code
41040
Manufacturer
Panasonic
Product group
Fire alarm systems › Control equipment
Weight
2240 g
Dimensions
290 × 235 × 75 mm
Operating temperature
0…+40 °C
Operating voltage
24 V DC (permitted 23.5–24.5 V DC), mains adapter included
Current consumption
80–700 mA
COM loop
24 V DC, max. 350 mA
Connection
USB (PC), COM loop in/out, earth
Address range
001–253
Short-circuit isolator
Yes
Material
Aluminium enclosure
Humidity
Max. 95% RH, non-condensing
Standards
EN 61000-6-3, EN 61000-6-1, EN 50581

Documents

Original manufacturer documents (PDF).

Technical datasheets

Certificates and declarations

More products in this product group

Need help choosing products?

Our sales team will help you choose devices that suit the site and the existing system, and will prepare a quotation. Tell us about the system, the site and the quantities needed.

Contact sales +358 40 668 7641