Panasonic
Panasonic 5000SPFI EBL512 G3, 4 loops, 512 alarm points
Product code 41030
Addressable EBL512 G3 fire alarm control panel with four COM loops and up to 512 alarm points. The panel includes a fire brigade panel and can be connected to a network of panels.
- 4 COM loops, each with up to 253 addresses
- Up to 1,012 addresses, of which up to 512 alarm points
- Sub-loops: up to 4 per COM loop (16 in total)
- Ring network of up to 30 panels over copper or fibre
- EN 54-2 and EN 54-4, CPR 0402-CPR-C500143 / C500142
- Battery space 2 × 12 V, 17–28 Ah; up to 65 Ah externally
✓ In quote request: pcs ·
✓ On your document list · Select and download documents
The product sheet opens in a new tab, where you can print or save it.
A quote or help choosing products? Sales+358 40 668 7641myynti@pap.fi
A technical question about a device? Technical support+358 40 668 7643tuki@pap.fi
Product description
Panasonic EBL512 G3 5000 is an addressable fire alarm control panel to which alarm points and other loop devices are connected via four COM loops. The panel shows fire alarms and faults on the fire brigade panel and on a graphical display, and it is operated from the keypad of the operating panel. The panel meets EN 54-2 and EN 54-4.
Capacity and connections
A total of 1,012 COM loop units (addresses) can be connected to the panel, of which up to 512 can be alarm points; the remaining addresses are available, for example, for alarm devices, I/O units and emergency and escape route luminaires. Each COM loop can take 253 addresses, and up to 128 short-circuit isolators can be connected to a loop. Each COM loop can have up to four sub-loops. The main board has four programmable, monitored 24 V voltage outputs (S0–S3), two programmable relay outputs (R0–R1), four programmable inputs (I0–I3) and changeover contact outputs for fire and fault transmission.
Network and commissioning
Several panels are connected to each other with the network board 5040 (EBL ring network, up to 30 panels, copper RS-422 or fibre) or with the TLON interface board 5090. Programming is done with the EBLWin software via the panel’s USB port, and a web server or gateway can be connected to the RS-232 port.
Installation
The panel is intended for dry indoor spaces (−5…+40 °C, IP30). Standby power is provided by two 12 V VRLA batteries (17–65 Ah); batteries over 28 Ah are placed outside the panel with a cable of no more than 2 metres. The cabinet can be mounted on a wall or in a 19" rack with the mounting plate 5020.
Technical data
- Product code
- 41030
- Manufacturer
- Panasonic
- Product group
- Fire alarm systems › Control equipment
- COM loop
- 4
- Sub-loops
- Max. 4 per COM loop (16 in total)
- Programmable voltage output
- 4 (S0–S3), 24 V DC, supervised, ≤ 0.5 A
- Relay output
- 2 programmable (R0–R1), NO/NC, 2 A / 30 V DC; plus changeover contacts for fire and fault routing
- Supervised input
- 4 programmable (I0–I3)
- Voltage output
- 6
- Weight
- 23.1 kg (without printer and batteries)
- Dimensions
- 628 × 438 × 187 mm (H × W × D)
- Battery
- 2 × 12 V VRLA, 17–28 Ah inside the panel; max. 2 × 65 Ah in an external battery enclosure
- IP rating
- IP30
- Operating temperature
- −5…+40 °C (indoor use only)
- EN 54 approval
- EN 54-2, EN 54-4, EN 54-13
- CPR
- 0402-CPR-C500143, 0402-CPR-C500142
- Capacity
- Max. 1,012 addresses, of which max. 512 alarm points; 253 addresses / COM loop
- Short-circuit isolators
- Max. 128 per COM loop
- COM loop current
- Max. 350 mA / COM loop, loop voltage 25.0 V ±1.5 V
- Operating voltage
- 230 V AC (195–253 V), 50 Hz; system voltage 24 V DC
- Material
- Metal enclosure, aluminium-zinc coating AZ150
- Colour
- Light grey (NCS S 1500-N) and aluminium
- Humidity
- Max. 95% RH, non-condensing
- VdS approval
- G210058
- Connection
- USB (B) for EBLWin programming; RS-232 for web server/gateway
- Network
- EBL Ring network (5040) max. 30 control panels or TLON (5090)
- Standards
- EN 54-2, EN 54-4; EMC EN 55032 (class A), EN 50130-4; LVD EN IEC 62368-1
Documents
Original manufacturer documents (PDF).
Technical datasheets
User manuals
Design guides
Certificates and declarations
- VdS system approval, no. S 214004
- VdS approval, no. G 210058
- CNBOP-PIB certificate of admittance (Poland), no. 5011/2023
- CPR certificate of constancy of performance, no. 0786-CPR-20982
- CPR certificate of constancy of performance, no. 0402-CPR-C500142
- CPR certificate of constancy of performance, no. 0402-CPR-C500143
- EU declaration of conformity, no. D09-MFST-290-09
- Declaration of performance (DoP), no. D09-MFST-P290-06
More products in this product group



- CommFront
Need help choosing products?
Our sales team will help you choose devices that suit the site and the existing system, and will prepare a quotation. Tell us about the system, the site and the quantities needed.

