Panasonic
Panasonic 4487RE addressable sounder, red
Product code 41398
Addressable wall-mounted sounder with a built-in short-circuit isolator. Seven tones and three priority levels, for example for pre-warning, fire alarm and heavy smoke alarm.
- Seven selectable tones, incl. DIN 33404 and NEN 2575
- Three priority levels, each with its own tone
- Low current consumption: quiescent 2 mA, alarm 10 mA
- Built-in short-circuit isolator, powered from the COM loop
- Supports automatic addressing
- Approved to EN 54-3 and EN 54-17
✓ In quote request: pcs ·
✓ On your document list · Select and download documents
The product sheet opens in a new tab, where you can print or save it.
A quote or help choosing products? Sales+358 40 668 7641myynti@pap.fi
A technical question about a device? Technical support+358 40 668 7643tuki@pap.fi
Product description
Panasonic 4487RE is a red addressable sounder that is mounted on the wall and connected to the COM loop. It has a built-in short-circuit isolator and takes its operating voltage from the loop. The sounder is approved to EN 54-3 and EN 54-17 and is intended for dry indoor areas.
The sounder has seven tones selectable in EBLWin: continuous and intermittent 984 Hz, alternating 644/984 Hz, the German DIN 33404 sweep, the Dutch NEN 2575, the French NFS 32-001 and the Australian T3. The highest minimum sound pressure level is approximately 90–94 dB(A) at a distance of 1 metre, depending on the tone, and the maximum sound level is 93 dB(A). Each of the three priority levels (high, medium and low) is programmed with its own control expression and tone, so the sounder can give a different tone for pre-warning, fire alarm and heavy smoke alarm, for example. A higher-priority condition changes the tone automatically.
The built-in short-circuit isolator does not require its own COM loop address and limits the effect of a short circuit to the faulty loop segment only. Current consumption is low: 2 mA in quiescent state and 10 mA in alarm.
Installation and compatibility
- Wall mounting, indoor use only
- Automatic addressing with EBLWin or manually with the 4414/4414E tool (address 001–253)
- Advanced mode: EBL512 G3 and EBL128 V ≥ 2.3, EBLOne V ≥ 3.3; in NORMAL mode as type 4477, in 2330 mode as type 3377
- Conductor size Ø 0.6–1.4 mm (0.3–1.5 mm²)
Technical data
- Product code
- 41398
- Manufacturer
- Panasonic
- Product group
- Fire alarm systems › Field devices › Alarm devices
- Colour
- Red
- Weight
- 240 g
- Dimensions
- 109 × 109 × 95 mm
- Sound output
- Highest minimum level approx. 90–94 dB(A) at 1 m (depending on tone)
- Operating temperature
- −10…+55 °C
- EN 54 approval
- EN 54-3, EN 54-17
- CPR
- 0786-CPR-21534
- Storage temperature
- −25…+70 °C
- Humidity
- Max. 95% RH, non-condensing
- Material
- Flame-retardant ABS and polycarbonate
- IP rating
- IP21
- Operating voltage
- 12–30 V DC (nominal 24 V DC)
- Current consumption (quiescent)
- 2 mA
- Current consumption (alarm)
- 10 mA
- Input power
- 0.02–0.3 W
- Frequency range
- 440–1,200 Hz depending on tone
- Tone types
- 7 tones, 3 priority levels
- Address range
- 001–253
- Short-circuit isolator
- Built-in
- Compatibility
- EBL512 G3, EBL128 V ≥ 2.3, EBLOne V ≥ 3.3
- Mounting
- Wall mounting, dry indoor areas
- Standards
- EN 61000-6-3, EN 50130-4, EN IEC 63000 (RoHS)
- Maximum sound output
- Max. 93 dB(A)
Documents
Original manufacturer documents (PDF).
Technical datasheets
More products in this product group



- Panasonic
Need help choosing products?
Our sales team will help you choose devices that suit the site and the existing system, and will prepare a quotation. Tell us about the system, the site and the quantities needed.