Panasonic 4462 I/O TVK two-input unit with short-circuit isolator

Panasonic

Panasonic 4462 I/O TVK two-input unit with short-circuit isolator

Product code 50018

Addressable two-input unit with short-circuit isolator, for example for monitoring sprinklers and other contacts. IP65 enclosure; the TVK version has additional terminals for the emergency lighting supply voltage.

  • Two general-purpose inputs for NO/NC contacts, supervised or unsupervised
  • For example for sprinkler monitoring
  • Built-in short-circuit isolator, automatic addressing
  • IP65 enclosure, approved to EN 54-17 and EN 54-18
  • Additional terminals for the emergency lighting supply voltage (TVK)

The product sheet opens in a new tab, where you can print or save it.

A quote or help choosing products? Sales+358 40 668 7641myynti@pap.fi

A technical question about a device? Technical support+358 40 668 7643tuki@pap.fi

Product description

Panasonic 4462 is an addressable two-input unit with a built-in short-circuit isolator. It is suitable, for example, for bringing status information from a sprinkler system or other equipment into the fire alarm system. The unit takes its operating voltage from the COM loop, and the inputs are programmed with EBLWin.

Inputs

The unit has two general-purpose inputs (Z/In0 and In2) for NO or NC contacts. The inputs can be programmed as supervised or unsupervised; a supervised NO input uses a 33 kΩ end-of-line resistor, so that an open circuit (over 43 kΩ) is reported as a fault. The unit has no relay outputs; the more versatile I/O unit is the 4461.

Installation

The unit is surface mounted on a wall or ceiling. Cables are brought in through the membrane entries of the housing; cable glands are not included. Addressing takes place automatically with EBLWin or manually with the 4414/4414E addressing tool. The unit works in Advanced mode with EBL512 G3 and EBL128 control panels from version 2.4 and with EBLOne control panels from version 3.3. The 4463 kit is available for DIN rail mounting.

TVK version

According to the product information, the TVK version has extra terminals for the emergency lighting power supply. In the MX emergency lighting system, the 4461/4462 I/O units are used for phase monitoring, among other things: the phase monitoring device is connected to the supervised input Z/In0 of the unit, so that the emergency luminaires can be activated in the event of a phase failure. The control output of the MX Power Box is also connected to an input of the 4461/4462 unit.

Technical data

Product code
50018
Manufacturer
Panasonic
Product group
Emergency lighting › Field devices
Dimensions
110 × 110 × 49 mm
Weight
188 g
Operating temperature
−10…+50 °C
Storage temperature
−20…+60 °C
Humidity
Max. 95% RH, non-condensing
IP rating
IP65
Colour
RAL 9010
Material
Polypropylene (Fibox JB 6 G)
Operating voltage
12–30 V DC (nominal 24 V DC)
Current consumption (quiescent)
≤ 2.2 mA
Current consumption (alarm)
≤ 2.2 mA
Inputs
2 general inputs NO/NC, supervised or unsupervised
Address range
001–253
Short-circuit isolator
Yes
Mounting
Surface mounting on wall or ceiling
Connection
Screw terminals, conductor 0.28–1.5 mm²
EN 54 approval
EN 54-17, EN 54-18
CPR
0786-CPR-21589
Standards
VdS 2344, VdS 2504, EN 61000-6-3, EN 50130-4, EN IEC 63000