Panasonic
Panasonic 4409 IP67 TVK heat detector
Product code 50028
Enclosed analogue heat detector for outdoor areas and damp indoor spaces, IP67. The TVK version has additional terminals for the emergency lighting supply voltage.
- Watertight IP67, operating temperature down to −20 °C
- Alarm classes A1, A2S and BS selectable with EBLWin
- Approved to EN 54-5
- Connections for an external indicator
- Additional terminals for the emergency lighting supply voltage (TVK)
- Addressable, connected directly to the COM loop
✓ In quote request: pcs ·
✓ On your document list · Select and download documents
The product sheet opens in a new tab, where you can print or save it.
A quote or help choosing products? Sales+358 40 668 7641myynti@pap.fi
A technical question about a device? Technical support+358 40 668 7643tuki@pap.fi
Product description
Panasonic 4409 is an enclosed analogue heat detector intended for outdoor use and damp indoor premises. The detector measures temperature with a thermistor in the range 0–100 °C in 0.5 °C steps. The detector housing is watertight (IP67). The detector must not be exposed to strong sunlight or to temperatures below −20 °C.
In NORMAL mode, one of three alarm classes in accordance with EN 54-5 is selected for the detector with EBLWin:
- A1: alarm at 56 °C (rate of rise ≤ 4 °C/min) or 46 °C (rate of rise > 4 °C/min)
- A2S: alarm at 60 °C
- BS: alarm at 74 °C
The detector indicator lights up in an alarm and flashes once a second for as long as no address has been set. One external indicator, for example 2218, can be connected to terminals E+ and E−.
Installation
The detector is mounted on the ceiling on a junction box, into which the cables are brought through compression glands; for cables under 6 mm, the rubber tube supplied is used. The COM loop address (001–253) and mode are set with address setting tool 4414/4414E before connection to the loop. The detector works with EBL512 G3, EBLOne and EBL128 control panels. Test equipment such as Solo or Testifire can be used for testing.
TVK version
According to the product information, the TVK version has extra terminals for the emergency lighting power supply. This allows the 24 V emergency lighting supply line to be routed through the device along the same route as the COM loop, for example when MX emergency luminaires and exit signs are used.
Technical data
- Product code
- 50028
- Manufacturer
- Panasonic
- Product group
- Emergency lighting › Field devices
- Dimensions
- Ø 100 × 78 mm
- Weight
- 112 g
- Operating temperature
- −20…+50 °C (A1, A2S), −20…+65 °C (BS)
- Storage temperature
- −45…+70 °C
- Humidity
- Max. 95% RH, non-condensing
- IP rating
- IP67
- Colour
- Grey (Munsell N8)
- Material
- Modified polycarbonate
- Operating voltage
- 12–30 V DC (nominal 24 V DC)
- Current consumption (quiescent)
- 0.185 mA
- Current consumption (alarm)
- 2.3 mA (≤ 3.65 mA with external indicator)
- Alarm temperature
- A1: 56 °C / 46 °C, A2S: 60 °C, BS: 74 °C
- Address range
- 001–253
- Short-circuit isolator
- No
- Mounting
- Ceiling mounting on a junction box
- Connection
- Conductor 0.3–1.13 mm², external indicator E+/E−
- EN 54 approval
- EN 54-5 (A1, A2S, BS)
- CPR
- 0786-CPR-21764
- VdS approval
- G 222045 (valid until 3 November 2026)
- Standards
- VdS 2344, VdS 2543, EN 61000-6-3, EN 50130-4, EN IEC 63000
Documents
Original manufacturer documents (PDF).
More products in this product group
Need help choosing products?
Our sales team will help you choose devices that suit the site and the existing system, and will prepare a quotation. Tell us about the system, the site and the quantities needed.