Panasonic
Panasonic 3312FLW TVK mounting base with push-in terminals and E+/E− connection
Product code 50025
White analogue mounting base for Panasonic addressable detectors and for MX emergency luminaires and exit signs. Push-in terminals for the COM loop and the E+/E− connection.
- Mounting base for MX emergency luminaires, exit signs and analogue detectors
- Push-in terminals for the COM loop and the E+/E− terminal pair
- Cable entry from above or from the side
- Recess for an address label holder
- Ceiling mounting, or wall mounting with MX luminaires
✓ In quote request: pcs ·
✓ On your document list · Select and download documents
The product sheet opens in a new tab, where you can print or save it.
A quote or help choosing products? Sales+358 40 668 7641myynti@pap.fi
A technical question about a device? Technical support+358 40 668 7643tuki@pap.fi
Product description
Panasonic 3312FLW is a white analogue mounting base that is connected to the COM loop. Panasonic analogue heat, smoke and multi-sensor detectors (types 33xx, 43xx and 44xx) as well as MX series emergency luminaires and exit signs can be installed in the base. The base is intended for dry indoor premises.
The base has push-in terminals (blue connector) for the COM loop in and out and a second pair of push-in terminals (grey connector, E+ and E−), to which an external indicator, for example 2218, is connected when the base is used with a detector. Cables can be brought into the base from above or from the side. The base has a recess for address label holder 3390, so the zone address or technical number can be read even when the detector is in place.
MX emergency luminaires
MX25, MX40 and MX Light luminaires are installed in base 3312FLW (or 3312W). In this case, both the COM loop and the emergency lighting supply line are connected to the base, and the luminaire is locked to the base with a hexagon socket screw. With MX luminaires, the base can be mounted on the ceiling or on the wall.
Installation
When used with a detector, the base is mounted on the ceiling. Screws are not included. The conductor size for the push-in terminals is 0.28–1.2 mm². Protective cover 3313 is available for the base.
Technical data
- Product code
- 50025
- Manufacturer
- Panasonic
- Product group
- Emergency lighting › Field devices
- Dimensions
- Ø 102 × 15 mm
- Operating temperature
- −10…+50 °C
- Storage temperature
- −20…+70 °C
- Humidity
- Max. 95% RH, non-condensing
- IP rating
- IP51
- Colour
- White (Munsell 10Y9/0.5)
- Material
- ABS
- Operating voltage
- 12–30 V DC (nominal 24 V DC)
- Current consumption (quiescent)
- 0 mA
- Mounting
- Ceiling mounting (wall mounting also possible with MX luminaires)
- Weight
- 47 g
- Connection
- Push-in terminals: COM loop (blue), external indicator E+/E− (grey); conductor 0.28–1.2 mm²
- Compatibility
- Analogue detectors 33xx/43xx/44xx; MX emergency and exit luminaires
- Standards
- EN 61000-6-3, EN 50130-4