Panasonic
Panasonic 4461 TVK addressable I/O unit
Product code 50017
Addressable multi-function I/O unit with short-circuit isolator: supervised input (also usable as a zone input for conventional detectors), opto-isolated input, general-purpose input and two relay outputs in an IP65 enclosure.
- Supervised input for conventional detectors or general use (Z/In0)
- Opto-isolated input (6–30 V DC) and general-purpose input
- Two programmable relay outputs, 2 A / 30 V DC
- Built-in short-circuit isolator, automatic addressing
- IP65 enclosure, approved to EN 54-17 and EN 54-18
- Additional terminals for the emergency lighting supply voltage (TVK)
✓ In quote request: pcs ·
✓ On your document list · Select and download documents
The product sheet opens in a new tab, where you can print or save it.
A quote or help choosing products? Sales+358 40 668 7641myynti@pap.fi
A technical question about a device? Technical support+358 40 668 7643tuki@pap.fi
Product description
Panasonic 4461 is an addressable multi-function I/O unit with a built-in short-circuit isolator. The unit is connected to the COM loop, from which it also takes its operating voltage, and all inputs and outputs are programmed with EBLWin.
Inputs and outputs
- Supervised input Z/In0: either a zone input for conventional detectors and manual call points (short-circuit and open-circuit monitoring in accordance with EN 54-13, 10 µF end-of-line capacitor, max. 32 alarm points) or a general-purpose input for an NO/NC contact. An optical beam detector or a flame detector, for example, can also be connected via the input.
- Opto-isolated input In1, activated by an external voltage of 6–30 V DC.
- General-purpose input In2 for an NO/NC contact, supervised with a 33 kΩ end-of-line resistor.
- Two relay outputs Re0 and Re1 (NO/NC), for example for closing fire doors.
Installation
The unit is surface mounted on a wall or ceiling. Cables are brought in through the membrane entries of the housing; cable glands are not included. Addressing takes place automatically with EBLWin or manually with the 4414/4414E addressing tool. The short-circuit isolator is in use in Advanced mode (EBL512 G3 and EBL128 from version 2.4, EBLOne from version 3.3). In NORMAL mode, the unit works like model 3361. The 4463 kit is available for DIN rail mounting.
TVK version
According to the product information, the TVK version has additional terminals for the emergency lighting supply voltage. In the MX emergency lighting system, the 4461/4462 I/O units are used for phase monitoring, among other things: the phase monitoring device is connected to the supervised input Z/In0 of the unit, so that the emergency luminaires can be activated in the event of a phase failure. The control output of the MX Power Box is also connected to an input of the 4461/4462 unit.
Technical data
- Product code
- 50017
- Manufacturer
- Panasonic
- Product group
- Emergency lighting › Field devices
- Dimensions
- 110 × 110 × 49 mm
- Weight
- 188 g
- Operating temperature
- −10…+50 °C
- Storage temperature
- −20…+60 °C
- Humidity
- Max. 95% RH, non-condensing
- IP rating
- IP65
- Colour
- RAL 9010
- Material
- Polypropylene (Fibox JB 6 G)
- Operating voltage
- 12–30 V DC (15–30 V when used as a zone input), nominal 24 V DC
- Current consumption (quiescent)
- ≤ 4.3 mA
- Current consumption (alarm)
- ≤ 15 mA
- Inputs
- 1 supervised (zone or general input), 1 opto-isolated, 1 general input
- Outputs
- 2 relays NO/NC, 2 A / 30 V DC
- Address range
- 001–253
- Short-circuit isolator
- Yes (Advanced mode)
- Mounting
- Surface mounting on wall or ceiling
- Connection
- Screw terminals, conductor 0.28–1.5 mm²
- EN 54 approval
- EN 54-17, EN 54-18
- CPR
- 0786-CPR-21579
- Standards
- VdS 2344, VdS 2504, EN 61000-6-3, EN 50130-4, EN IEC 63000
Documents
Original manufacturer documents (PDF).
More products in this product group
Need help choosing products?
Our sales team will help you choose devices that suit the site and the existing system, and will prepare a quotation. Tell us about the system, the site and the quantities needed.