Panasonic 3000-115 Fireray 3000 Ex d, ATEX

Panasonic

Panasonic 3000-115 Fireray 3000 Ex d, ATEX

Product code 41606

Flameproof end-to-end beam detector system for smoke detection in large hazardous areas. The system comprises an Ex d transmitter and receiver and a controller installed in a safe area.

  • Transmitter and receiver in Ex d enclosures, ATEX
  • Measuring distance 10–80 m
  • Controller in a safe area, max. 2 detectors
  • Laser alignment for single-person installation
  • Light Cancellation technology, contamination compensation
  • EN 54-12

The product sheet opens in a new tab, where you can print or save it.

A quote or help choosing products? Sales+358 40 668 7641myynti@pap.fi

A technical question about a device? Technical support+358 40 668 7643tuki@pap.fi

Product description

Panasonic 3000-115 is the Fireray 3000 Ex d, an end-to-end infrared beam detector for protecting large hazardous areas. The system detects smouldering and heavily smoking fires at an early stage, which flame detectors may not detect. It is designed for large spaces such as oil platforms, refineries and explosives stores.

The system comprises a transmitter, a receiver, a controller, fixings and two brackets. The transmitter and receiver are ATEX-certified Ex d enclosures for Group II hazardous areas. The controller is installed in a safe area, so adjustment and testing can be carried out from outside the hazardous area. The sensitivity (25–60%) and the alarm and fault delay (2–30 s) are set on the LCD display of the controller. The requirements of EN 54-12 are met with a sensitivity of 25% and an alarm delay of no more than 20 seconds. Light Cancellation technology and compensation for contamination and building movement reduce false alarms.

Installation

The measuring distance is 10–80 m. The receiver has laser alignment, and both ends have fine adjustment wheels. Two detector pairs can be connected to the controller (additional pack 3000-026), each with its own fire and fault relay. The controller can also power the transmitter. Ex d cable glands are used for cable entries. Protective cage 1000-019 is available as an accessory.

Technical data

Product code
41606
Manufacturer
Panasonic
Product group
Fire alarm systems › Field devices › Beam detectors
Colour
Transmitter and receiver red, control unit white
Dimensions
Transmitter/receiver 172 × 149 × 190 mm, control unit 124 × 203 × 73.5 mm
Weight
Control unit 606 g, transmitter 3.7 kg, receiver 3.7 kg
Operating voltage
12–36 V DC
Operating temperature
−10…+55 °C (EN 54-12), −20…+55 °C (ATEX)
IP rating
Control unit IP54, transmitter/receiver IP66
EN 54 approval
EN 54-12
ATEX certificate
Sira 15ATEX1260X
ATEX classification
II 2 GD Ex db op is IIC T6 Gb Ex tb IIIC T85°C Db Ta = -20°C to +55°C
Material
Copper-free aluminium alloy LM25, steel brackets
Current consumption (quiescent)
Control unit 14 mA, transmitter 8 mA
Humidity
93% RH, non-condensing
Beam range
10–80 m
Connection
3 × 20 mm cable entries, Ex d cable glands (e.g. Peppers E3WBF)
CPR
0786-CPR-21669
Relays
VFCO 2 A / 30 V DC, fire and fault per detector

Documents