Panasonic
Panasonic 2814 ATEX manual call point CCP-E-IS
Product code 41570
Intrinsically safe (Ex ia) conventional manual call point for hazardous areas. The call point is based on Hochiki’s KAC World Series housing and operates with either a breakable glass element or a non-breaking plastic element.
- ATEX II 1 G, Ex ia IIC T4
- Breakable glass or non-breaking plastic element
- Terminals for single-core conductors up to 2.5 mm²
- Robust design, KAC World Series housing
- GL type approval
✓ In quote request: pcs ·
✓ On your document list · Select and download documents
The product sheet opens in a new tab, where you can print or save it.
A quote or help choosing products? Sales+358 40 668 7641myynti@pap.fi
A technical question about a device? Technical support+358 40 668 7643tuki@pap.fi
Product description
Panasonic 2814 is Hochiki’s CCP-E-IS, an intrinsically safe (IS) conventional manual call point for hazardous areas. The call point is based on the widely used KAC World Series housing and is used together with IS smoke and heat detectors on the same detector circuit in the hazardous area.
The call point can be fitted with either a breakable glass element or a non-breaking plastic element. The design is robust, and the terminals accept single-core conductors up to 2.5 mm². The call point is ATEX rated II 1 G Ex ia IIC T4, so it is suitable for category 1 gas areas and all lower categories. Temperature class T4 means that the surface temperature of the device does not exceed 135 °C. The call point also has GL type approval.
Installation
The IS detector circuit is connected to the fire alarm control panel via a Zener barrier or galvanic isolator located in the safe area. An unlimited number of IS manual call points can be connected to the circuit, and they are always connected at the start of the circuit, before the detectors. Up to 20 IS detectors can be connected to the same circuit. A weatherproof IP67 version of the call point, CCP-W-IS, is also available.
Technical data
- Product code
- 41570
- Manufacturer
- Panasonic
- Product group
- Fire alarm systems › Field devices › Ex detectors
- ATEX classification
- II 1 G Ex ia IIC T4
- Connection
- Max. 2.5 mm² solid conductor
- Operating element
- Breakable glass or non-breakable plastic element
- Standards
- GL type approval
Documents
Original manufacturer documents (PDF).
Technical datasheets
More products in this product group



- Panasonic
Need help choosing products?
Our sales team will help you choose devices that suit the site and the existing system, and will prepare a quotation. Tell us about the system, the site and the quantities needed.