Securiton
Securiton ASD 531 aspirating smoke detector, 1 pipe
Product code 61301
Aspirating smoke detector for small monitoring areas. One sampling pipe, a pre-installed SSD 31 smoke sensor and commissioning on the device without software. EN 54-20, classes A, B and C.
- Tested to EN 54-20, classes A, B and C
- Monitoring area up to 720 m² and up to 75 m of pipe
- SSD 31 smoke sensor, alarm sensitivity 0.02–10 %/m
- Two slots for expansion modules
- Operating voltage 14–30 V DC, IP54
✓ In quote request: pcs ·
✓ On your document list · Select and download documents
The product sheet opens in a new tab, where you can print or save it.
A quote or help choosing products? Sales+358 40 668 7641myynti@pap.fi
A technical question about a device? Technical support+358 40 668 7643tuki@pap.fi
Product description
ASD 531 is an aspirating smoke detector in Securiton’s SecuriSmoke range for small monitoring areas. The detector’s fan draws air through the sampling holes of the sampling pipe and feeds it to the smoke sensor. Airflow monitoring detects pipe blockages and breakages. The pipe can be I-, U-, T-, H- or E-shaped.
The detector comes with a pre-installed SSD 31 smoke sensor with an alarm sensitivity of 0.02–10 %/m. Its three pre-signals are fixed at 30, 50 and 70% of the alarm threshold. Commissioning and settings are done with the rotary switches on the device (BasiConfig) without software. The pipe network can be designed with the ASD PipeFlow software.
The detector is connected to the fire alarm control panel via volt-free changeover contacts. The two expansion slots can take, for example, an RIM 36 relay module, which makes all three pre-signals and the sensor and pipe states available.
Technical data
- Product code
- 61301
- Manufacturer
- Securiton
- Manufacturer’s code
- ASD 531 (11-2000002-01-04)
- Product group
- Aspirating smoke detection › Detectors and sensors
- Operating voltage
- 14–30 V DC
- Current consumption (quiescent)
- ≈ 75 mA (24 V DC)
- Current consumption (alarm)
- ≈ 80 mA (24 V DC)
- Sampling pipes
- 1
- Sensors
- SSD 31 (included)
- Sensitivity range (alarm)
- 0.02–10%/m
- Detector class
- EN 54-20, classes A, B and C
- Monitoring area
- Up to 720 m²
- Maximum pipe length
- 75 m
- Maximum number of sampling holes
- A 6, B 8, C 12
- Sampling hole diameter
- 2–7 mm
- Expansion module slots
- 2 (RIM 36, XLM 35)
- Relays
- Fault and alarm, 50 V DC / 1 A / 30 W
- Sound pressure level
- 25 dB(A) / 1 m
- IP rating
- IP54
- Operating temperature
- −10…+55 °C
- Storage temperature
- −20…+70 °C
- Humidity
- 95% (briefly, non-condensing), 70% (continuously)
- Material
- ABS blend, UL 94-V0
- Dimensions
- 195 × 333 × 140 mm (W × H × D)
- Weight
- 1,950 g
- EN 54 approval
- EN 54-20
- VdS approval
- G 215100
- CPR
- 0786-CPR-21482
Documents
Original manufacturer documents (PDF).
Technical datasheets
Brochures
User manuals
Certificates and declarations
Other documents
Compatible products


- Securiton
- Securiton
Need help choosing products?
Our sales team will help you choose devices that suit the site and the existing system, and will prepare a quotation. Tell us about the system, the site and the quantities needed.