Panasonic
Panasonic 4400I analogue multi-sensor detector with short-circuit isolator, white
Product code 41312
Addressable analogue multi-sensor detector that combines an optical smoke detector and a heat detector. A built-in short-circuit isolator and AI-based fire decision reduce false alarms.
- Optical smoke and heat detection in one low-profile detector
- Built-in short-circuit isolator without its own address
- Learning function selects the alarm algorithm suited to the room
- Installation date stored in memory and automatic service signal
- Can also be used as a heat detector only (A1, A2S)
- Approved to EN 54-5, -7, -17 and -29 and by VdS (G217086)
✓ In quote request: pcs ·
✓ On your document list · Select and download documents
The product sheet opens in a new tab, where you can print or save it.
A quote or help choosing products? Sales+358 40 668 7641myynti@pap.fi
A technical question about a device? Technical support+358 40 668 7643tuki@pap.fi
Product description
Panasonic 4400I is a white addressable analogue multi-sensor detector that combines an optical smoke detector, a heat detector and a built-in short-circuit isolator in one low-profile housing. The detector is intended for dry indoor areas and works only in Advanced mode with EBL512 G3 (V ≥ 2.4) and EBLOne (V ≥ 3.3) control panels.
The fire decision is based on artificial intelligence that combines smoke density, a fixed temperature threshold and the rate of temperature rise. In this way, real fires are detected and false alarms caused by, for example, artificial smoke or oil mist can be reduced. Five room algorithms are available: normal, smoke/steam, clean, heater and cooking/welding. The learning function monitors local conditions for about a month and switches to a more suitable algorithm if necessary; for known rooms, the algorithm can also be set manually with EBLWin. The detector compensates for contamination automatically and gives a service signal when it needs to be replaced. It also stores its installation date, so the control panel can report an ageing detector.
The built-in short-circuit isolator divides the COM loop into segments, so a short circuit disables only the faulty segment. Two red LEDs flash in a fire alarm, and a green LED can indicate control panel polling, test mode or isolator activation.
Installation
- Installed in a 4412F base or a 4479 base sounder; not suitable for 3312x or 3379 bases
- Automatic addressing with EBLWin or manually with the 4414/4414E tool (address 001–253)
- Can be locked to the 4412F base with a hex socket screw (ordered separately)
- No external indicator connection in the detector; the 4418 remote indicator is connected via the base
Technical data
- Product code
- 41312
- Manufacturer
- Panasonic
- Product group
- Fire alarm systems › Field devices › Detectors
- Colour
- White (Munsell 10Y9/0.5)
- Weight
- 76 g
- Dimensions
- Ø 102 × 41 mm
- LED
- 2 red (alarm), 1 green (status)
- Operating temperature
- −10…+50 °C
- EN 54 approval
- EN 54-5, EN 54-7, EN 54-17, EN 54-29
- VdS approval
- G217086
- CPR
- 0786-CPR-21553
- Storage temperature
- −20…+70 °C
- Humidity
- Max. 96% RH, non-condensing
- Material
- Polycarbonate blend
- IP rating
- IP41
- Operating voltage
- 12–30 V DC (nominal 24 V DC)
- Current consumption (quiescent)
- 0.3 mA (+0.025 mA with green polling LED)
- Current consumption (alarm)
- 1.3 mA
- Alarm temperature
- 57 °C (multi mode); classes A1 and A2S in heat detector mode
- Address range
- 001–253
- Short-circuit isolator
- Built-in
- Compatibility
- Advanced mode: EBL512 G3 V ≥ 2.4, EBLOne V ≥ 3.3
- Mounting
- In base 4412F or base sounder 4479
- Standards
- EN 61000-6-3, EN 50130-4, EN IEC 63000 (RoHS)
Documents
Original manufacturer documents (PDF).
Technical datasheets
More products in this product group



- Panasonic
Need help choosing products?
Our sales team will help you choose devices that suit the site and the existing system, and will prepare a quotation. Tell us about the system, the site and the quantities needed.