Grey ASD 532 aspirating smoke detector from the front with the smoke level bar graph on the cover

Securiton

Securiton ASD 532 aspirating smoke detector, 1 pipe

Product code 61302

Aspirating smoke detector for small and medium-sized monitoring areas. One sampling pipe and a smoke level indicator. The SSD 532 smoke sensor is ordered separately. EN 54-20, classes A, B and C.

  • Tested to EN 54-20, classes A, B and C
  • Monitoring area up to 1,280 m² and up to 120 m of pipe
  • Smoke level bar graph display
  • Commissioning on the device (EasyConfig) or with ASD Config
  • Two slots for expansion modules, such as RIM 36 and SIM 35

The product sheet opens in a new tab, where you can print or save it.

A quote or help choosing products? Sales+358 40 668 7641myynti@pap.fi

A technical question about a device? Technical support+358 40 668 7643tuki@pap.fi

Product description

ASD 532 is an aspirating smoke detector in Securiton’s SecuriSmoke range for small and medium-sized monitoring areas. It has one sampling pipe and space for one SSD 532 smoke sensor, which is ordered separately. The measured smoke level is shown on the bar graph display on the cover. Airflow monitoring detects pipe blockages and breakages.

Commissioning and settings are done on the device (EasyConfig) or with the ASD Config software. The pipe network can be designed with ASD PipeFlow. The fan has three speed levels.

The two expansion slots can take an RIM 36 relay module, an SIM 35 network module or an XLM 35 loop module. With SIM 35, the detector can be connected to an RS-485 network and monitored centrally.

Technical data

Product code
61302
Manufacturer
Securiton
Manufacturer’s code
ASD 532 (11-2000003-01-04)
Product group
Aspirating smoke detection › Detectors and sensors
Operating voltage
14–30 V DC
Current consumption (quiescent)
≈ 100 mA (24 V DC)
Current consumption (alarm)
≈ 115 mA (24 V DC)
Sampling pipes
1
Sensors
SSD 532-3 (ordered separately)
Detector class
EN 54-20, classes A, B and C
Monitoring area
Up to 1,280 m²
Maximum pipe length
120 m
Maximum number of sampling holes
A 8, B 12, C 16
Sampling hole diameter
2–7 mm
Expansion module slots
2 (RIM 36, SIM 35, XLM 35)
Display
Smoke level bar graph
Sound pressure level
25 / 31 / 39 dB(A) / 1 m (fan levels I / II / III)
IP rating
IP54
Operating temperature
−20…+60 °C
Storage temperature
−30…+70 °C
Material
ABS blend, UL 94-V0
Dimensions
195 × 333 × 140 mm (W × H × D)
Weight
2,000 g (with SSD 532 sensor)
EN 54 approval
EN 54-20, EN 54-27
VdS approval
G 215101
CPR
0786-CPR-21483

Documents

Original manufacturer documents (PDF).

Technical datasheets

Brochures

Installation guides

User manuals

Certificates and declarations

Other documents

Compatible products

Need help choosing products?

Our sales team will help you choose devices that suit the site and the existing system, and will prepare a quotation. Tell us about the system, the site and the quantities needed.

Contact sales +358 40 668 7641