Panasonic 4452W conventional optical smoke detector

Panasonic

Panasonic 4452W conventional optical smoke detector

Product code 41441

Conventional optical smoke detector that is particularly good at detecting the large, light-coloured smoke particles of a smouldering fire. Connected to a detection zone of the fire alarm control panel via mounting base 2324.

  • Conventional optical smoke detector for a detection zone
  • Reliably detects the large, light-coloured smoke particles of a smouldering fire
  • Intelligent alarm algorithm and contamination compensation
  • Insect mesh and optical labyrinth reduce false alarms
  • Approved to EN 54-7 and by VdS (G213028)

The product sheet opens in a new tab, where you can print or save it.

A quote or help choosing products? Sales+358 40 668 7641myynti@pap.fi

A technical question about a device? Technical support+358 40 668 7643tuki@pap.fi

Product description

Panasonic 4452W is a white conventional optical smoke detector connected to a conventional detection zone of the fire alarm control panel. The detector is particularly good at detecting large, light-coloured smoke particles, which are produced in a smouldering fire, for example. It is intended for dry indoor premises and can be used in EBL512 G3, EBL128 and EBL512 systems.

Smoke enters the detector chamber through an insect mesh and an optical labyrinth. The design improves smoke inflow and condenses steam and mist into moisture on the chamber surfaces, which reduces false alarms. An AI-based fire decision adjusts sensitivity and delay according to changes in smoke; the alarm threshold is 4%/m and the delay is normally 9 seconds. The detector automatically compensates for contamination so that sensitivity remains constant.

Installation

The detector is fitted in conventional mounting base 2324, whose LED lights up in an alarm. The detection zone and any external indicator are connected to the base, and an end-of-line device matching the control panel and zone input is connected to the last device in the zone. The detector is pressed into the base with the markings aligned and turned clockwise. The conductor size for the base is Ø 0.65–1.6 mm (0.3–2 mm²). Operation can be tested with, for example, Solo or Testifire test equipment.

Technical data

Product code
41441
Manufacturer
Panasonic
Product group
Fire alarm systems › Field devices › Conventional detectors
Colour
White (Munsell 10Y9/0.5)
Weight
85 g
Dimensions
Ø 102 × 38 mm
LED
In base 2324
Operating temperature
−10…+50 °C
EN 54 approval
EN 54-7
VdS approval
G213028
CPR
0786-CPR-21252
Storage temperature
−25…+70 °C
Humidity
Max. 95% RH, non-condensing
Material
Modified polycarbonate
IP rating
IP41
Operating voltage
12–30 V DC (nominal 24 V DC)
Current consumption (quiescent)
0.04 mA
Current consumption (alarm)
Min. 3 mA
Alarm threshold
4%/m
Short-circuit isolator
No
Compatibility
EBL512 G3, EBL128, EBL512 (detection zone)
Mounting
In conventional base 2324
Standards
EN 61000-6-3, EN 50130-4, EN IEC 63000 (RoHS)