Skip to content
PAP Group, part of ProseroPAP Group, part of Prosero
Search the site

Suggested searches

Quick links

Request a quote
MenuClose
ASD 535-4 aspirating smoke detector from the front with the smoke level display

Securiton

Securiton ASD 535-4 aspirating smoke detector, 2 pipes

Product code 61307

Aspirating smoke detector for medium-sized and large monitoring areas. Two sampling pipes and a smoke level display; the SSD 535-3 sensors are ordered separately. EN 54-20, classes A, B and C.

  • Tested to EN 54-20, classes A, B and C
  • Monitoring area up to 5,760 m², up to 2 × 300 m of pipe
  • Space for two SSD 535-3 sensors, alarm sensitivity 0.02–10 %/m
  • Four expansion module slots (RIM 35, SIM 35, XLM 35, MCM 35)
  • IP54, operating temperature −30…+60 °C

The product sheet opens in a new tab, where you can print or save it.

A quote or help choosing products? Sales+358 40 668 7641myynti@pap.fi

A technical question about a device? Technical support+358 40 668 7643tuki@pap.fi

Product description

ASD 535-4 is an aspirating smoke detector in Securiton’s SecuriSmoke range for medium-sized and large monitoring areas. It has two sampling pipes and space for two SSD 535-3 smoke sensors, which are ordered separately. The measured smoke level is shown on the bar graph display on the cover. Airflow monitoring detects pipe blockages and breakages.

Commissioning and settings are done on the device (EasyConfig) or with the ASD Config software. The pipe network can be designed with ASD PipeFlow. The fan has five speed levels.

The four expansion slots can take RIM 35 relay modules (up to two), an SIM 35 network module, an XLM 35 loop module and an MCM 35 memory card module. In the two-pipe model each pipe has its own smoke sensor, so the pipe network in alarm can be identified.

Technical data

Product code
61307
Manufacturer
Securiton
Manufacturer’s code
ASD 535-4 (11-2000018-01-02)
Product group
Aspirating smoke detection › Detectors and sensors
Operating voltage
10.5–30 V DC
Current consumption (quiescent)
≈ 290 mA (24 V DC)
Current consumption (alarm)
≈ 385 mA (24 V DC)
Sampling pipes
2
Sensors
2 × SSD 535-3 (ordered separately)
Sensitivity range (alarm)
0.02–10%/m
Sensitivity range (pre-signals)
0.002–9%/m
Detector class
EN 54-20, classes A, B and C
Monitoring area
Up to 5,760 m²
Maximum pipe length
2 × 300 m
Maximum number of sampling holes
A 2 × 18, B 2 × 56, C 2 × 120
Sampling hole diameter
2–7 mm
Expansion module slots
4 (RIM 35, SIM 35, XLM 35, MCM 35)
Display
Smoke level bar graph
Sound pressure level
34–41 dB(A) / 1 m (fan levels I–V)
IP rating
IP54
Operating temperature
−30…+60 °C
Storage temperature
−30…+70 °C
Material
ABS blend, UL 94-V0
Dimensions
265 × 397 × 148 mm (W × H × D)
Weight
3,555 g (with sensor)
EN 54 approval
EN 54-20, EN 54-27
VdS approval
G 208154
CPR
0786-CPR-20600

Documents

Original manufacturer documents (PDF).

Technical datasheets

Brochures

Installation guides

User manuals

Certificates and declarations

Other documents

Compatible products

Need help choosing products?

Our sales team will help you choose devices that suit the site and the existing system, and will prepare a quotation. Tell us about the system, the site and the quantities needed.

Contact sales +358 40 668 7641