ELKO HRN-43N/400V phase monitoring relay

Product code 50008

Voltage monitoring relay for three-phase networks (ELKO HRN-43N/400V) for star connection 3 × 400/230 V. Monitors overvoltage and undervoltage, phase sequence, phase failure and asymmetry.

  • Star connection 3 × 400/230 V with neutral conductor
  • Overvoltage and undervoltage at two separate levels
  • Phase sequence, phase failure and adjustable asymmetry
  • 2 changeover contacts 16 A, operating separately or in parallel
  • Adjustable delay 0.1–10 s, selectable hysteresis 5/10%
  • Galvanically isolated 400 V AC supply

The product sheet opens in a new tab, where you can print or save it.

Order using the order form

A quote or help choosing products? Sales+358 40 668 7641myynti@pap.fi

A technical question about a device? Technical support+358 40 668 7643tuki@pap.fi

Product description

ELKO HRN-43N/400V is a voltage monitoring relay for three-phase networks with a neutral conductor (star connection 3 × 400/230 V). The relay monitors phase voltages at two separate levels (upper and lower limit), phase sequence, phase failure and asymmetry between phases. Each fault condition is shown by its own LED indicator. The relay’s supply voltage is a galvanically isolated 400 V AC.

Operation

The upper limit Umax is set between 138 and 276 V and the lower limit Umin at 35–99% of the upper limit. If any phase leaves the set range, the output contact opens after an adjustable delay (0.1–10 s); the delay filters out short dips and spikes. If two or three phases fail, the contacts open immediately. The asymmetry limit is adjusted between 5 and 20%, and the monitoring can be switched off. DIP switches are used to select the operation of the outputs (separately for overvoltage and undervoltage, or in parallel), a hysteresis of 5% or 10%, and the memory function.

Applications

The monitoring relay is used to protect equipment from mains disturbances and to control functions, such as starting standby power, in a fault situation. In emergency lighting systems, the phase monitoring relay can be used to ensure that the emergency lighting is activated if any phase fails; for example, according to the technical description of Panasonic MX emergency luminaires, the phase monitoring device is connected to a monitored input of I/O unit 4461/4462.

Installation

The relay is mounted on a DIN rail (EN 60715), and the mounting position is free. The outputs are two changeover contacts (16 A / AC1, 250 V AC).

Technical data

Product code
50008
Manufacturer
ELKO
Product group
Emergency lighting › Accessories
Operating voltage
400 V AC (50–60 Hz), −15%/+10%
Input power
Max. 5 VA / 2.5 W
Monitored mains supply
3 × 400/230 V, 50–60 Hz (L1-L2-L3-N)
Upper limit setting
138–276 V
Lower limit setting
35–99% of the upper limit
Asymmetry
Adjustable 5–20% or off
Delay
Fixed t1 max. 200 ms; adjustable t2 0.1–10 s
Hysteresis
Selectable 5% / 10%
Output
2 changeover contacts (AgNi), 16 A / AC1, 250 V AC / 24 V DC
Operating temperature
−20…+55 °C
Dimensions
90 × 52 × 65 mm
Weight
248 g
IP rating
IP40 (front panel), IP20 (terminals)
Mounting
DIN rail (EN 60715)
Connection
Conductors max. 1 × 2.5 mm² or 2 × 1.5 mm²
Standards
EN 60255-1, EN 60255-26, EN 60255-27

Documents

Original manufacturer documents (PDF).

Technical datasheets

Installation guides

More products in this product group

Ordering supplies or spare parts?

You can order supplies and spare parts directly using the order form. If you are not sure which product is right, ask our sales team.

Order using the order form +358 40 668 7641