> Panasonic PAVA-8003LN voice alarm panel, 16 lines, 1,500 W
> Source: https://pap.fi/en/tuote/pava-8003ln/
> Full site in machine-readable form (in Finnish): https://pap.fi/llms-full.txt
> Pages in English: https://pap.fi/llms.txt

# Panasonic PAVA-8003LN voice alarm control panel, 16 lines, 1,500 W, wall-mounted

Product code PAVA-8003LN

Wall-mounted PAVA voice alarm control panel: 16 loudspeaker lines (8 × AB), a total load capacity of 1,500 W rms and three simultaneous messages. Touchscreen, fire brigade microphone, amplifiers and power supply in the same enclosure.

-   Approved to EN 54-16 and EN 54-4, CPR 1438-CPR-1146 and 1438-CPR-0527
-   16 loudspeaker lines (8 × AB), 1,500 W rms
-   Amplifiers 3 × 500 W, standby amplifier in case of amplifier failure
-   Touchscreen and fire brigade microphone
-   Extended network card: 2 × SFP, RS485 and PoE

## Product description

PAVA-8003LN is a wall-mounted panel in Panasonic’s PAVA voice alarm system. The same enclosure houses the control unit with its touchscreen, the fire brigade microphone, the amplifiers and the power supply. The panel has 16 loudspeaker lines (8 × AB), a total load capacity of 1,500 W rms and three simultaneous messages.

The standby amplifier keeps announcements running if an amplifier fails. According to Panasonic’s technical datasheet, the 8003 series has three 500 W transformerless class D amplifiers. All three can be used simultaneously, giving a total output of up to 1,500 W. The loudspeaker lines can be monitored by impedance measurement, loop isolators or end-of-line modules. The panel has been tested and approved to EN 54-16 and EN 54-4 (CPR 1438-CPR-1146). It is Ambient System’s midiVES 8003LN sold under Panasonic’s product name, so the manufacturer’s CPR certificate 1438-CPR-0527 (EN 54-16 and EN 54-4) also covers it. Batteries are ordered separately.

PAVA exchanges alarm and fault information with Panasonic’s EBL fire alarm system over a supervised TCP/IP connection. According to Panasonic, the panel is easy to connect to SIP and IP intercom systems.

The extended network card of the N model is intended for larger or distributed systems in which the panels are connected over long distances, by optical fibre or with redundant network connections. The card has a LAN/WAN port for programming and integrations, two LAN ports (one with PoE), an RS485 port, two slots for optional SFP modules and two freely programmable logic inputs and outputs.

The first digit of Panasonic’s model code is the number of A/B zones (8). When the lines are wired directly rather than as A/B pairs, the number of zones can be doubled. The last digit indicates the number of simultaneous messages. Letters: L = touchscreen, N = extended network card, R = rack-mounted model.

## Technical data

- **Product code:** PAVA-8003LN
- **Manufacturer:** Panasonic
- **Product group:** Voice alarm systems › Control equipment
- **Mounting:** Wall mounting
- **Loudspeaker lines:** 16 (8 × AB)
- **Total load capacity:** 1,500 W rms
- **Amplifiers:** 3 × 500 W
- **Standby amplifier:** Yes
- **Simultaneous messages:** 3
- **Touchscreen:** Yes
- **Fire brigade microphone:** Yes, handheld microphone
- **Network card:** Extended (N): 1 × LAN/WAN, 2 × LAN (one with PoE), RS485, 2 × SFP slots, 2 logic inputs and 2 logic outputs
- **Message memory:** SD card (512 MB included, over 20 min of messages), max. 32 GB
- **Control inputs and outputs:** 7 logic inputs and 3 relay outputs
- **Power supply:** 230 V AC
- **Battery capacity:** 4 × 65 Ah
- **Batteries:** Ordered separately
- **IP rating:** IP30
- **Operating conditions:** −5…+40 °C, humidity 5–95% (non-condensing)
- **Dimensions:** 797 × 442 × 241 mm (H × W × D)
- **Weight:** 31 kg (gross)
- **EN 54 approval:** EN 54-16, EN 54-4
- **CPR:** 1438-CPR-1146 (Panasonic PAVA), 1438-CPR-0527 (Ambient miniVES/midiVES)

## Documents

Original manufacturer documents (PDF).

### Technical datasheets

-   [Product catalogue (series): PAVA voice alarm system](https://pap.fi/liitteet/valmistajat/panasonic-fire-security__en_cat_pava_mew03121_rev_.pdf) PDF · English · 3.9 MB
-   [Technical datasheet (series): PAVA voice alarm system](https://pap.fi/liitteet/valmistajat/panasonic-fire-security__en_td_pava_mew03049_rev_.pdf) PDF · English · 9.9 MB
-   [Datasheet (series): miniVES/midiVES voice alarm system (Ambient System)](https://pap.fi/liitteet/valmistajat/ambient-system__20230602_mini_VES-midiVES_ds_en.pdf) PDF · English · 4.5 MB

### Brochures

-   [Brochure (series): PAVA voice alarm control panels](https://pap.fi/liitteet/valmistajat/panasonic-fire-security__ll_pava_mew03050_rev_.pdf) PDF · English · 322 kB
-   [Brochure (series): miniVES/midiVES voice alarm system (Ambient System)](https://pap.fi/liitteet/valmistajat/ambient-system__Brochure-miniVESmidiVES_en_02082021.pdf) PDF · English · 2.8 MB

### User manuals

-   [User manual (series): miniVES/midiVES voice alarm system, short guide](https://pap.fi/liitteet/valmistajat/ambient-system__20261021_miniVES_midiVES_um_short_en.pdf) PDF · English · 2.2 MB
-   [User manual (series): miniVES/midiVES voice alarm system](https://pap.fi/liitteet/valmistajat/ambient-system__20231127_miniVES_midiVES_um_en.pdf) PDF · English · 44.5 MB

### Certificates and declarations

-   [CPR certificate (series): 1438-CPR-0527, miniVES/midiVES system](https://pap.fi/liitteet/valmistajat/ambient-system__1438-CPR-0527.pdf) PDF · multilingual · 5.9 MB
-   [Declaration of performance (DoP) (series): miniVES/midiVES system mini\_midiVES-20260720](https://pap.fi/liitteet/valmistajat/ambient-system__Declaration-of-Performance_mini_midiVES_DOP_20072026.pdf) PDF · multilingual · 4.0 MB
-   [EU declaration of conformity (series): miniVES/midiVES system mini\_midiVES-DCE-20230120](https://pap.fi/liitteet/valmistajat/ambient-system__miniVES_midiVES_DCE_EN.pdf) PDF · English · 731 kB