> Panasonic Grizzle AE2010G-S aspirating smoke detector
> Source: https://pap.fi/en/tuote/panasonic-ae2010g-s-grizzle/
> Full site in machine-readable form (in Finnish): https://pap.fi/llms-full.txt
> Pages in English: https://pap.fi/llms.txt

# Panasonic Aspect Grizzle AE2010G-S aspirating smoke detector, stand-alone, standard sensitivity

Product code 60101

Stand-alone Aspect aspirating smoke detector with Grizzle sensors (B/C). Two detection areas, built-in power supply and battery space. EN 54-20, classes B and C.

-   Tested to EN 54-20 (classes B and C) and EN 54-4, CPR 0786-CPR-21084
-   Grizzle sensor kit SENSORKIT-G: B/C, standard
-   Two detection areas, up to 2 × 100 m of pipe
-   Connected to a conventional zone input via a 4461 unit
-   Built-in 230 V AC power supply, space for a backup battery
-   Configuration with the Aspect Tool B app (BLE), IP44

## Product description

AE2010G-S is a Panasonic Aspect series aspirating smoke detector with two Grizzle optical smoke sensors. Each pipe has its own detection chamber, so the detector distinguishes two detection areas. The device has a built-in power supply, filters and space for a backup battery. The enclosure is anodised aluminium, and the overpressurised design keeps dust and moisture away from the electronics.

The detector has the SENSORKIT-G sensor kit (B/C). It is the standard model. Sensitivity can be set per area and separately for day and night with the Aspect Tool B app, which connects to the detector via Bluetooth (BLE).

The stand-alone model is connected to a conventional zone input of the fire alarm control panel via a 4461 unit. The panel receives fire and fault signals but cannot distinguish between the areas; the area in alarm is shown on the detector’s front panel. According to Panasonic’s datasheet, the stand-alone version is ordered by replacing P with S in the order code.

## Technical data

- **Product code:** 60101
- **Manufacturer:** Panasonic
- **Manufacturer’s code:** AE2010G-S
- **Product group:** Aspirating smoke detection › Detectors and sensors
- **Operating voltage:** 230 V AC, 50 Hz (optionally 12–24 V DC)
- **Current consumption:** Average 500 mA, peak 1.7 A
- **Sampling pipes:** 2
- **Sensors:** 2 × Grizzle (SENSORKIT-G, B/C)
- **Detector class:** EN 54-20, classes B and C
- **Maximum pipe length:** 2 × 100 m
- **Battery:** Internal 7 Ah or 18 Ah (LiFePO4)
- **Sound pressure level:** 55 dB / 1 m (45–50 dB with AU 002)
- **Bluetooth:** BLE (Aspect Tool B)
- **IP rating:** IP44
- **Operating temperature:** −30…+55 °C
- **Humidity:** Max. 98%
- **Material:** Aluminium profile, PC/ABS ends
- **Dimensions:** 272 × 530 × 143 mm (W × H × D)
- **Weight:** 6.6 kg
- **EN 54 approval:** EN 54-20, EN 54-4
- **CPR:** 0786-CPR-21084
- **VdS approval:** G218069

## Documents

Original manufacturer documents (PDF).

### Technical datasheets

-   [Datasheet: Grizzle AE2010G-P, AE2010G-S](https://pap.fi/liitteet/valmistajat/panasonic-fire-security__ll_ae2010g_p_mew01856_rev_2.pdf) PDF · English · 126 kB
-   [Technical datasheet: Aspect AE2010](https://pap.fi/liitteet/valmistajat/panasonic-fire-security__en_td_ae2010_mew01855_rev_16.pdf) PDF · English · 8.5 MB
-   [Product catalogue (series): Aspect AE2010 accessories](https://pap.fi/liitteet/valmistajat/panasonic-fire-security__ll_ae2010_acc_mew01860_rev_11.pdf) PDF · English · 1.8 MB

### Brochures

-   [Brochure (series): Aspect aspirating smoke detection system](https://pap.fi/liitteet/valmistajat/panasonic-fire-security__en_cat_ae2010_mew02788_rev_4.pdf) PDF · English · 11.5 MB