# Panasonic 4479-B addressable base sounder

Product code 41399

Addressable base sounder for the 4400I multi-sensor detector. Brings a 90 dB(A) alarm sound into the same space as the detector; seven tones and three priority levels.

-   Sound level 90 ± 3 dB(A), seven selectable tones
-   Three priority levels, each with its own tone
-   Low-power mode: approx. 84 dB(A) and max. 1.5 mA
-   Push-in terminals for the loop, auxiliary conductors X1/X2 and the cable screen
-   Automatic addressing together with the 4400I
-   Approved to EN 54-3 and by VdS (G218002)

## Product description

Panasonic 4479-B is a matt black addressable base sounder that is mounted on the ceiling and connected to the COM loop. The 4400I analogue multi-sensor detector is installed in the base, so the alarm sound is provided in the same space as the detector. The base cannot be used without a detector, because the short-circuit isolator is in the detector and without it the loop remains open. The product is intended for dry indoor areas.

The sounder has seven tones, including continuous and intermittent 984 Hz, the German DIN 33404 sweep, the Dutch NEN 2575 and the French NFS 32-001. Each of the three priority levels is programmed in EBLWin with its own control expression and tone. For example, a fire alarm elsewhere in the building can give one tone, an alarm on the same floor another, and an alarm from the base’s own detector a third. In normal mode, the sound pressure level is 90 ± 3 dB(A) (tone 6: 87 dB(A)), approved to EN 54-3. The selectable low-power mode (approx. 84 dB(A), max. 1.5 mA) reduces current consumption, but it is not approved to EN 54-3.

### Installation

-   Ceiling mounting, screws not included; the detector can be locked to the base with a screw
-   When cables are brought in from above through a suspended ceiling, the 4489 seal is used (IP21)
-   Automatic addressing together with the 4400I or manually with the 4414/4414E tool; the detector must have a different address
-   Advanced mode: EBL512 G3 and EBL128 V ≥ 2.4, EBLOne V ≥ 3.3
-   Conductor size Ø 0.6–1.385 mm (0.28–1.5 mm²)

## Technical data

- **Product code:** 41399
- **Manufacturer:** Panasonic
- **Product group:** Fire alarm systems › Field devices › Alarm devices
- **Colour:** Matt black (Munsell N1.5)
- **Weight:** 102.5 g
- **Dimensions:** 160 × 102 × 25.4 mm
- **Sound output:** 90 ± 3 dB(A) (tone 6: 87 ± 3 dB(A)); low-power mode approx. 84 dB(A)
- **Operating temperature:** −10…+55 °C
- **EN 54 approval:** EN 54-3
- **VdS approval:** G218002
- **CPR:** 0786-CPR-21564
- **Storage temperature:** −20…+70 °C
- **Humidity:** Max. 95% RH, non-condensing
- **Material:** ABS
- **IP rating:** IP21C
- **Operating voltage:** 12–30 V DC (nominal 24 V DC)
- **Current consumption (quiescent):** ≤ 0.75 mA
- **Current consumption (alarm):** Max. 3.5 mA (low-power mode max. 1.5 mA)
- **Input power:** 9–105 mW
- **Frequency range:** 440–1,200 Hz depending on tone
- **Tone types:** 7 tones, 3 priority levels
- **Address range:** 001–253
- **Short-circuit isolator:** No (isolator in detector 4400I)
- **Connection:** Push-in terminals SAi, SAo, SB, X1, X2 and cable screen
- **Compatibility:** EBL512 G3, EBL128 V ≥ 2.4, EBLOne V ≥ 3.3
- **Mounting:** Ceiling mounting, detector 4400I in the base
- **Standards:** EN 61000-6-3, EN 50130-4, EN IEC 63000 (RoHS)

## Documents

Original manufacturer documents (PDF).

### Technical datasheets

-   [Technical datasheet: 4479-B addressable base sounder](https://pap.fi/liitteet/tuotteet/en_td_4479_mew02073_rev_8.pdf) PDF · English · 1.8 MB

### Certificates and declarations

-   [EU declaration of conformity, no. ESSC-F00029-03](https://pap.fi/liitteet/tuotteet/doc_4479_essc_f00029_03.pdf) PDF · English · 596 kB
-   [Declaration of performance (DoP), no. 0786-CPR-21564](https://pap.fi/liitteet/tuotteet/dop_4479_essc_fp0029_02.pdf) PDF · multilingual · 136 kB
-   [CPR certificate of constancy of performance, no. 0786-CPR-21564](https://pap.fi/liitteet/tuotteet/cpr_4479_0786_cpr_21564.pdf) PDF · multilingual · 463 kB valid until further notice
-   [VdS approval, no. G 218002](https://pap.fi/liitteet/tuotteet/vds_4479_g218002_exp_2029_02_06.pdf) PDF · multilingual · 843 kB valid 7 February 2025 – 6 February 2029