# Panasonic 4414E address setting tool

Product code 42111

Battery-powered handheld tool for setting the address and operating mode of Panasonic analogue detectors and other addressable COM loop devices before they are connected to the loop.

-   Sets and reads the COM loop address (001–253) and operating mode
-   Resets the device to address 000 for automatic addressing
-   Suggests a suitable mode for a new device (NORMAL or Advanced)
-   Battery life approx. 250 h or up to 50,000 read and write operations
-   Automatic switch-off adjustable to 10–99 seconds
-   Crocodile clip cable included for wired and screw-terminal devices

## Product description

Panasonic 4414E is an address setting tool for setting the loop address (001–253) and operating mode of analogue detectors and other addressable COM loop devices. The address and mode must be set before the device is connected to the COM loop. The tool can also read the current address and mode of a device and reset the device to address 000, which is used when the EBL system addresses the devices automatically.

There are four operating modes: M0 (NORMAL), M1 (2330), M2 (2312) and M3 (Advanced). For a new device, the tool suggests either NORMAL or Advanced mode depending on the device type, and for a used device, the mode last used. Advanced mode is blocked for devices that do not support it. When several devices are programmed one after another, the address can be incremented by one with the 0/+1 button.

### Connection

The contact pins (SA/SB) of an analogue detector are pressed directly into the push-in terminals of the tool. Devices with wire leads or screw terminals only are connected with the cable supplied, which has insulated crocodile clips and push-in terminals.

### Power supply

The tool is powered by four 1.5 V alkaline batteries (LR6/AA). The batteries last approximately 250 hours or up to 50,000 read or write operations, and a low battery is indicated on the display. By default, the tool switches off after 30 seconds of inactivity; the time can be adjusted between 10 and 99 s. The tool is intended for indoor use in dry premises.

## Technical data

- **Product code:** 42111
- **Manufacturer:** Panasonic
- **Product group:** Fire alarm systems › Accessories
- **Weight:** 320 g with batteries, 220 g without batteries
- **Dimensions:** 153 × 68 × 42 mm (H × W × D)
- **Battery:** 4 × 1.5 V alkaline (LR6/AA)
- **Operating temperature:** 0…+40 °C
- **Battery life:** Approx. 250 h or 50,000 read/write operations
- **Operating voltage:** 4.5–6 V DC
- **Current consumption (quiescent):** 0 mA
- **Current consumption (active):** 8.5 mA
- **Humidity:** Max. 95% RH, non-condensing
- **IP rating:** IP42
- **Material:** ABS plastic
- **Colour:** Black / light green (RAL 6027)
- **Address range:** 001–253 (plus reset to address 000)
- **Operating modes:** M0 NORMAL, M1 2330, M2 2312, M3 Advanced
- **Standards:** EN 61000-6-3, EN 50130-4, EN IEC 63000

## Documents

Original manufacturer documents (PDF).

### Technical datasheets

-   [Technical datasheet: Panasonic 4414E address setting tool](https://pap.fi/liitteet/valmistajat/panasonic-fire-security__en_td_4414e_mew02093_rev_3.pdf) PDF · English · 953 kB
-   [Product brochure: Panasonic 4414E address setting tool](https://pap.fi/liitteet/valmistajat/panasonic-fire-security__ll_4414_mew02157_rev_2.pdf) PDF · English · 169 kB

### Certificates and declarations

-   [EU declaration of conformity, no. ESN-F00300-07](https://pap.fi/liitteet/tuotteet/doc_4414_esn_f00300_07.pdf) PDF · multilingual · 521 kB