# Panasonic 3364 I/O unit, supervised 24 V outputs

Product code 41370

Addressable voltage output unit with two supervised 24 V DC outputs for alarm devices and one output for closing fire doors. Connected to the COM loop and an external 24 V supply.

-   Two programmable, supervised 24 V DC outputs for alarm devices
-   Separate 24 V DC output for fire door holding magnets
-   Door output is cut approx. 30 s after a mains or loop fault
-   Outputs max. 1 A continuous
-   Approved to EN 54-18, CPR 0786-CPR-21201
-   DIN rail mounting with the 3363 accessory

## Product description

Panasonic 3364 is an addressable unit with two supervised voltage outputs for Panasonic EBL fire alarm control panels. The unit is connected to the COM loop, and the operating voltage for the outputs is taken from an external 24 V DC power supply. It is suitable, for example, for controlling sounders and beacons and for releasing fire door holding magnets in dry indoor areas.

The unit has three outputs. VO0 and VO1 are programmable and supervised, intended for sounders, beacons and other alarm devices. Line supervision is based on 470 nF capacitors, and the value is calibrated from the control panel menu; an open circuit, a short circuit or a deviation from the calibrated value is reported as a fault. VO2 is an unsupervised output for closing fire doors. It is controlled by a control expression, and it also cuts the voltage after approximately 30 seconds if the /Mains OK input reports a mains fault or communication on the COM loop is lost. The outputs are programmed with the EBLWin software.

### Installation and compatibility

-   The address (001–253) is set with the 4414 address setting tool
-   Compatible with EBL512 G3, EBL128 and EBL512 (V ≥ 2.2)
-   Wall or ceiling mounting, 10 cable entries in the cover
-   DIN rail mounting with the 3363 adapter kit
-   One 5098 end-of-line device is required for each supervision capacitor
-   Conductor size Ø 0.6–1.6 mm (0.28–2 mm²)

## Technical data

- **Product code:** 41370
- **Manufacturer:** Panasonic
- **Product group:** Fire alarm systems › Field devices › I/O units
- **Weight:** 110 g (with protective cover 155 g)
- **Dimensions:** 90 × 70 × 32 mm (with protective cover 129 × 73 × 45 mm)
- **Operating voltage:** 12–30 V DC from the loop (nominal 24 V DC); external supply 18–30 V DC
- **Operating temperature:** −10…+55 °C
- **EN 54 approval:** EN 54-18
- **CPR:** 0786-CPR-21201
- **Storage temperature:** −20…+60 °C
- **Humidity:** Max. 95% RH, non-condensing
- **Colour:** Dark grey
- **Material:** Flame-retardant ABS and polycarbonate
- **IP rating:** IP54
- **Current consumption (quiescent):** < 6 mA
- **Current consumption (alarm):** < 6 mA
- **Outputs:** VO0 and VO1 supervised, VO2 unsupervised; each max. 1 A (10 ms 1.4 A)
- **Address range:** 001–253
- **Short-circuit isolator:** No
- **Mounting:** Surface mounting on wall or ceiling, DIN rail with accessory 3363
- **Standards:** EN 61000-6-3, EN 50130-4, EN IEC 63000 (RoHS)

## Documents

Original manufacturer documents (PDF).

### Technical datasheets

-   [Technical datasheet: Panasonic 3364 I/O unit](https://pap.fi/liitteet/tuotteet/en_td_3364_mew01900_rev_3.pdf) PDF · English · 748 kB

### Certificates and declarations

-   [CPR certificate of constancy of performance, no. 0786-CPR-21201](https://pap.fi/liitteet/tuotteet/cpr_3364_0786_cpr_21201.pdf) PDF · multilingual · 1.4 MB valid until further notice
-   [EU declaration of conformity, no. ESSC-F00014-10](https://pap.fi/liitteet/tuotteet/doc_3364_essc_f00014_10.pdf) PDF · English · 245 kB
-   [Declaration of performance (DoP), no. 0786-CPD-21201 (document ID ESSC-FP0014-7)](https://pap.fi/liitteet/tuotteet/dop_3364_essc_fp0014_07.pdf) PDF · multilingual · 106 kB