# Panasonic 2840 intrinsically safe addressable smoke detector

Product code 41575

Addressable, intrinsically safe (IS) optical smoke detector for hazardous areas. Connected to the COM loop of a Panasonic fire alarm control panel via the 2842 IS isolator unit.

-   Addressable IS smoke detector for zones 0, 1 and 2
-   ATEX II 1 G Ex ia IIC T5 Ga
-   Approved to EN 54-7, VdS G223018
-   Six selectable alarm algorithms
-   Up to 20 detectors per 2842 IS isolator unit
-   IP22, IP44 with the 2843 mounting box

## Product description

Panasonic 2840 is an addressable, intrinsically safe optical smoke detector for hazardous (Ex) areas. It works like the Panasonic 4301 analogue optical smoke detector: the detector detects smoke by means of infrared light scattering. The detector is ATEX rated II 1 G Ex ia IIC T5 Ga and is suitable for zones 0, 1 and 2.

The alarm algorithm is selected in EBLWin from six options (H-15, N-15, L-15, H-35, N-35, L-35), which adapt the sensitivity (2.4–3.6% smoke density) and detection time (15 or 35 s) to the site. The default is N-15. According to the manufacturer, the L-15, H-35, N-35 and L-35 algorithms may not meet the requirements of EN 54-7. The detector’s indicator lights up in a fire alarm.

### Installation

The detector is mounted on the ceiling in the Ex area either on its own (IP22) or in the 2843 waterproof IS mounting box (IP44). It is connected to the IS COM line, which runs from the 2842 IS isolator unit installed in the safe area. Up to 20 IS detectors can be connected to one IS COM line, and the line can be up to 500 m long. The address (001–253) and NORMAL mode are set with the 4414/4414E address setting tool before connection. The detector is compatible with EBL512 G3, EBL128 and EBLOne control panels (version 3.3 onwards) and is configured as type 4301.

## Technical data

- **Product code:** 41575
- **Manufacturer:** Panasonic
- **Product group:** Fire alarm systems › Field devices › Ex detectors
- **Colour:** Grey (Munsell N8)
- **Weight:** 300 g
- **Dimensions:** Ø 102 × 62 mm
- **LED:** Red
- **Operating temperature:** −10…+55 °C
- **EN 54 approval:** EN 54-7
- **ATEX certificate:** DEKRA 11ATEX0107 X
- **CPR:** 0786-CPR-21783
- **ATEX classification:** II 1 G Ex ia IIC T5 Ga
- **Material:** Flame-retardant ABS and polycarbonate
- **Operating voltage:** 16 V DC (permitted 15–17.3 V DC), IS COM line
- **Current consumption (quiescent):** ≤ 0.3 mA
- **Current consumption (alarm):** ≤ 1.5 mA
- **IP rating:** IP22, IP44 with mounting box 2843
- **Storage temperature:** −25…+70 °C
- **Humidity:** Max. 95% RH, non-condensing
- **Address range:** 001–253
- **ATEX zone:** 0 / 1 / 2
- **VdS approval:** G223018

## Documents

Original manufacturer documents (PDF).

### Technical datasheets

-   [Technical datasheet: 2840–2843 intrinsically safe addressable detectors](https://pap.fi/liitteet/tuotteet/en_td_2840_2841_2842_2843_mew01874_rev_11.pdf) PDF · English · 1.2 MB

### Certificates and declarations

-   [CPR certificate of constancy of performance, no. 2831-CPR-F2748](https://pap.fi/liitteet/tuotteet/cpr_2840_2831_cpr_f2748.pdf) PDF · English · 194 kB valid until further notice
-   [CPR certificate of constancy of performance, no. 0786-CPR-21783](https://pap.fi/liitteet/tuotteet/cpr_2840_0786_cpr_21783.pdf) PDF · multilingual · 1.8 MB valid until further notice
-   [EU-type examination certificate (ATEX), no. DEKRA 11ATEX0107 X, issue 3](https://pap.fi/liitteet/tuotteet/dekra_2840_2841_11atex0107_iss_3.pdf) PDF · English · 2.3 MB
-   [EU declaration of conformity, no. ESSC-F00017-10](https://pap.fi/liitteet/tuotteet/doc_2840_essc_f00017_10.pdf) PDF · English · 281 kB
-   [Declaration of performance (DoP), no. ESSC-FP0017-12](https://pap.fi/liitteet/tuotteet/dop_2840_essc_fp0017_12.pdf) PDF · English · 122 kB